2007-03-30 10:54:33 | ****** UNSAT ***** |
| |
| ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| |
| ** PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH SOME |
| INFORMATION AS NEEDED FOR REVIEW, ONLY A REVIEW OF |
| SUBMITTED PLANS COULD BE DONE. |
| |
| 1) NOTE: PLEASE PROVIDE ELECTRICAL DETAIL FOR L ANY NEW |
| LOADS, IF EXISTING PLEASE INDICATE HOW THESE ARE BEING |
| FED. PLEASE INDICATE THE BREAKER AND CONDUCTOR SIZES |
| WHICH ARE NEW OR EXISITNG. IF NO NEW LODAS ARE BEING |
| ADDED, THEN PLEASE INDICATE. |
| PLEASE SUBMIT A DETAIL FOR ANY NEW WIRING OF THE SPA |
| AND ASSOCIATED EQUIPMENT. |
| NEED TO VERIFY WIRING, SIZE, LOAD, OVER CURRENT |
| PROTECTION ETC. |
| 240.4, 408.4, 310.16 |
| |
| FBC 106.3.5.1.2 |
| |
| 2) NOTE: PLEASE SEE MISSING DETAIL FOR NEW LIGHT, HOW |
| IS THIS BEING FED? IS THIS LOW VOLTAGE, SIZE OF |
| TRANSFORMER, NEW OR EXISTING AND SIZE OF THE NEW |
| CONDUCTORS BEING ADDED. |
| |
| 3) NOTE: PLEASE SEE MISSING EQUIPOTENTIAL BONDING GRID |
| PER 680.26 |
| |
| ** PLEASE KNOW THAT ANY ADDITIONAL PANEL SCHEDULE, WIHT |
| BREAKER INFORMATION AND WIRING ON PANEL SCHEDULE MAY BE |
| DONE BY THE ELECTRICAL CONTRACTOR WHICH HAS ALREADY |
| BEEN IN CONTACT WITH THIS OFFICE. |
| PLEASE SEE THAT THE COMMENTS FOR 2 AND 3 NEEDS TO BE |
| DONE BY THE ENGINEERING FIRM. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |