2007-06-28 15:07:07 | |
| |
| *** UNSAT 2ND REVIEW *** |
| |
| |
| 1) NOTE: PLEASE SEE SPECIFICALLY THE PREVIOUS REVIEW |
| NOTED **IMPORTANT** WHICH REQUESTED ALL OF THE |
| OLD/VOIDED SHEETS TO BE REMOVED FROM SETS AND TO SUBMIT |
| THEM SEPARATELY. |
| THIS WAS NOT DONE, PLEASE SEE THE SAME REQUEST STANDS. |
| |
| 2) NOTE:SAME NOTE AS PREVIOUS REVIEW. |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUPPLY MORE INFORMATION FOR ELECTRICAL, WHERE IT |
| IS BEING FROM? HOW AND WHERE ARE DISCONNECTING MEANS> |
| (SPECIFIC DISTANCES ETC). |
| PLEASE SEE COMMENTS WHICH WERE GIVEN TO OWNER?S |
| REPRESENTATIVE FOR REQUIRE INFORMATION SHOWING ALL |
| CLASS AND DIVISION LOCATIONS. |
| PLEASE SEE 514.11 ETC. |
| FBC 106.1.2 (ADMIN SECTION FOR ADDITIONAL |
| INFORMATION). |
| |
| 3) NOTE: SAME NOTE. PLEASE SEE THE REQUIRED LICENSE |
| INFORMATION WAS NOT PLACED ON TITLE BLOCKS AS |
| REQUIRED. |
| PLEASE SEE THE TITLE BLOCKS NOW CONTAIN A NEW ENGINEER |
| WHICH ADDRESSING AND INFORMATION ON TITLE BLOCKS DOES |
| NOT COORDINATE WITH THE STATE WEBSITE. |
| PLEASE KNOW PLANS MAY BE RETAINED AND FORWARDED TO THE |
| FLORIDA BOARD OF PROFESSIONAL ENGINEERS. |
| FAC 61G15-23.002, FS 471.023 |
| |
| ** PREVIOUS REVIEW NOTE** |
| PLEASE SEE MISSING INFORMATION FOR TITLE BLOCKS FOR |
| BOTH OFTHE ENGINEERING FIRMS AS REQUIRED UNDER |
| FLORIDA ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA |
| STATUTES 471.023. |
| PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND |
| PRINTED LICENSE NUMBER OF THE PE. |
| PLEASE ALSO SEE MISSING THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| ** PLEASE SEE THE INFORMATION AS LISTED ON THE STATE OF |
| FLORIDA'S WEBSITE DOES NOT CORRELATE WITH PLANS FOR |
| "CORE STATES ENGINEERING". |
| ** PLEASE KNOW THAT ONE SET OF PLANS WILL BE RETAINED |
| BY THIS OFFICE. |
| |
| 4) NOTE: PLEASE COORDINATE APPLICATIONS AND D SCOPE OF |
| WORK AS APPLIED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW THAT AT THIS TIME THE PERMIT APPLICATION IS |
| BEING MADE UNDER A CBC LICENSE FOR A FUEL PERMIT WHICH |
| IS TO BE VERIFIED FOR SCOPE AND WHETHER OR NOT THIS |
| TYPE OF PERMIT CAN BE APPLIED FOR UNDER THE CBC LICENSE |
| AND SCOPE AS SHOWN ON PLANS. PLEASE KNOW OTHER SUB WORK |
| WILL REQUIRE ADDITIONAL PERMIT APPLICATIONS FOR SUB |
| SCOPE OF WORK. ONCE MAIN PERMIT IS ISSUED AND THOSE SUB |
| TRADE REVIEWS ARE PASSED, THEN THE SUB CONTRACTOR CAN |
| SIMPLY APPLY FOR PERMIT, REFERENCE THE MAIN PLANS AND |
| PAY SUB PERMIT FEE AND BE ISSUED A PERMIT THE SAME |
| DAY/TIME. |
| |
| 5) NOTE: SAME NOTE. THE VALUE ISLOW AND A VALUE WILL |
| MAY BE ASSESSED BY THIS OFFICE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW THAT THE COMPLETE SCOPE OF WORK FOR THE |
| FUEL TANK, PUMPS, ELECTRICAL, ETC SHALL INCLUDE ALL |
| LABOR AND MATERIALS EVEN IF EQUIPMENT, PUMPS TANK(S) |
| ETC ARE OWNER SUPPLIED. |
| PLEASE ADJUST THE APPLIED VALUE FOR ALL WORK AS SHOWN. |
| |
| 6) NOTE:PLEASE SEE THE PLANS NOW CONTAIN AS NEW |
| ENGINEER OF RECORD. PLEASE SEE THE SEAL IS NOT CLEAR |
| AND VISIBLE WITH ALL INFORMATION ON SAID SEAL AS |
| REQUIRE PER FAC 61G15-23.001. |
| PLEASE SEE THE PLANS ALSO APPEAR TO BE SIGNED WITH |
| *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE OF |
| THE DESIGNER OF RECORD PLEASE SUBMIT A SIGNED, DATED, |
| SEALED AND NOTARIZED LETTER FOR SIGNATURE VERIFICATION. |
| THIS WILL BE PLACED IN OUR SIGNATURE FILE FOR FUTURE |
| REFERENCE. |
| FS 471.025 |
| |
| 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENT FOR CODE COMPLIANCE AS SOME OF THE NOTES |
| FORM PREVIOUS REVIEW STILL REMAIN. |
| PLEASE SEE THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |