Plan Review Notes
Plan Review Notes For Permit 07020557
Permit Number 07020557
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-25 14:36:06****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004 W/2005, 2006
 AMEND
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FACFLORIDA ADMINISTRATIVE CODE
 FSFLORIDA
  
 FROM PREVIOUS LIST:
  
 1.-2.)ADDRESSED.
  
 3.)APPLICATION STATES INGROUND, PLANS ARE ABOVE
 GROUND.APPLICATION TO BE CONSISTENT WITH THE PLANS.
  
 4.)SEPARATE PERMITS REQUIRED.
  
 5-7.)ADDRESSED.
  
 8.)ALL INFORMATION REQUIRED BY FAC61G15-23.002 IS TO
 BE ON EACH SHEET.
  
 NEW COMMENT:
  
 9.)SHEET 2 OF 2, ENGINEERING NOTES DECLARE AN
 IMIPORTANCE FACTOR OF .87.PLESAE SEE FBC TABLE 1604.5
 AND CLARIFY HOW FAILURE OF A FUEL TANK IS "LOW HAZARD".
  
  