Plan Review Notes For Permit 07020557 |
Permit Number |
07020557 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-16 15:56:13 | -----------------DENIED------------------- | | | | 1. APPLICATION FOR A FUEL PERMIT IS TO BE SUBMITTED BY | | A LICENSED POLLUTION STORAGE SYSTEMS CONTRACTOR OR | | MECHANICAL CONTRACTOR AS DEFINED IN FS 489.105(3) | | | | 2. PLEASE ADJUST PROJECT DESCRIPTION ON PERMIT | | APPLICATION TO ACCURATELY REFLECT THE SCOPE OF WORK. | | APPLICATION STATES "INGROUND" TANK BUT THE PLANS | | INDICATE THE TANK WILL BE ABOVE GROUND. | | | | 3. SHEET ONE FUEL TANK DETAILS IS A COPY AND IS OF POOR | | QUALITY WHICH HAS CAUSED SOME OF THE SMALLER WRITING TO | | BE ILLEGIBLE. FBC 106.1.1. | | | | 4. SHEET 1 APPLICABLE CODES: #4 REFERENCES THE STANDARD | | BUILDING CODE. THIS APPLICATION HAS BEEN SUBMITTED | | UNDER THE FBC 2004 W/ 2006 REVISIONSS. SHEET 2 | | ENGINEERING NOTES ALSO CITES THE WRONG CODE BODY. | | PLEASE ADJUST AND RESUBMIT. | | | | 5. SHEET 2 ENGINEERING NOTES: THE LOCATION OF THE | | PROPOSED WORK IS WITHIN THE 140MPH BASIC WIND SPEED | | ZONE PER FBC FIG 1609. | | | | 6. PLEASE SEE ELECTRICAL PLAN REVIEW COMMENTS #3 AND 6 | | REGARDING | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|