2007-03-31 17:53:17 | *****DENIED***** | | | | | | 1.THE NUMERICAL ADDRESS SHALL BE IN THE TITLE BLOCK | | OF EACH SUBMITTED PLAN SHEET.SEE ADDRESS MISSING | | E-01, E-02, AND THE (3) EZ FUEL & TANK SOLUTIONS | | SHEETS. | | | | 2.PLANS INDICATE THAT THIS WILL BE AN ABOVE GROUND | | TANK BUT THE THE APPLICATION IS FOR AN INGROUND TANK. | | PLEASE CLARIFY. | | | | 3.NFPA 30 AND 30A, 2003 EDITION SHALL BE REFERENCED. | | | | 4.EMERGENCY RESPONSE IDENTIFICATION NEEDED. A SIGN OR | | MARKING THAT MEETS THE REQUIREMENT OF NFPA 704 SHALL BE | | VISIBLE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|