2007-03-15 12:00:07 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM |
| BEACH GAS PERMIT APPLICATION REQUIREMENTS; RESIDENTIAL |
| GENERATOR PERMIT APPLICATION REQUIREMENTS; |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. UNTIL THE ZONING ISSUE IS RESOLVED GAS PERMIT CAN |
| NOT BE ISSUED DUE TO THE FACT THAT THE GENERATORS |
| PLACEMENT MIGHT CHANGE. |
| |
| 2. THE SUBMITTED MANUFACTURER SPECIFICATIONS HAVE |
| PROPANE INDICATED AS THE FUEL SOURCE AND THE SUBMITTED |
| GAS PERMIT APPLICATION AND PLANS ARE INDICATING NATURAL |
| GAS AS THE FUEL SOURCE. PLEASE CORRELATE AND RESUBMIT. |
| |
| 3. THE SUBMITTED MANUFACTURER SPECIFICATIONS FOR THE |
| GENERATOR ARE INDICATING THE NATURAL GAS BTU LOAD AS |
| 560,000 AND THE SUBMITTED GAS DRAWINGS ARE INDICATING |
| THE GENERATOR BTU LOAD AS 548,000. PLEASE CORRECT THE |
| GAS DRAWINGS TO REFLECT THE GENERATOR MANUFACTURER |
| SPECIFICATIONS AND CORRECT THE TOTAL BTU LOAD OF |
| 1,197,000 ON THE RESUBMITTAL. |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| 5. THE SUBMITTED NOTICE OF COMMENCEMENT IS INCORRECT |
| AND VOID. PLEASE PROVIDE A CURRENT NOTICE OF |
| COMMENCEMENT RECORDED WITH THE CLERK OF THE COURT. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |