2008-02-08 13:35:46REVISION: "OK" CHANGED LAYOUT AND ADDED GENERATOR.
 REFERENCE GEN/RES PERMIT #07110219.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION
 AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE
 ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE
 PROTECTED IN AN APPROVED MANNER.
 B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE
 COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND
 WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND
 SHALL BE FACTORY APPLIED.
 C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING
 UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED
 UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT
 WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS
 SECTION.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,900 CUBIC FEET REQUIRED.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]