Plan Review Notes For Permit 07020476 |
Permit Number |
07020476 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-03-06 11:29:48 | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 404.8 PROTECTION | | AGAINST CORROSION: METALLIC PIPE EXPOSED TO CORROSIVE | | ACTION, SUCH AS SOIL CONDITION OR MOISTURE SHALL BE | | PROTECTED IN AN APPROVED MANNER. | | B} PER FBC-2004 FUEL GAS, SECTION 404.8.2 PROTECTIVE | | COATINGS AND WRAPPING: PIPE PROTECTIVE COATINGS AND | | WRAPPINGS SHALL BE APPROVED FOR THE APPLICATION AND | | SHALL BE FACTORY APPLIED. | | C} PER FBC-2004 FUEL GAS, SECTION 404.11 PIPING | | UNDERGROUND BENEATH BUILDINGS: PIPING INSTALLED | | UNDERGROUND BENEATH BUILDINGS IS PROHIBITED EXCEPT | | WHERE THE PIPING IS SLEEVED IN ACCORDANCE WITH THIS | | SECTION. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED | | PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,900 CUBIC FEET REQUIRED. |
|