Date |
Text |
2007-02-26 14:58:26 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH |
| GAS PERMIT APPLICATION REQUIREMENTS; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND |
| THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: PLEASE INDICATE THE BTU LOADS OF THE APPLIANCES |
| ON THE RESUBMITTAL. |
| |
| 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| NOTE: CLEARLY INDICATE THE DELIVERY PRESSURE ON THE |
| RESUBMITTAL. THERE ARE TWO DELIVERY PRESSURES INDICATED |
| ON THE SUBMITTED DRAWINGS, ONE IS 21 LB AND THE OTHER |
| IS O.5 PSI, PLEASE CLARIFY ON THE RESUBMITTAL WITH ONLY |
| INDICATING ONE DELVERY PRESSURE. |
| |
| 3. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL IF THE |
| GAS PIPING IS ABOVE GROUND OR UNDERGROUND, AND WHAT GAS |
| PIPING IS EXISTING OR NEW. |
| |
| ******IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |