Plan Review Notes
Plan Review Notes For Permit 07020476
Permit Number 07020476
Review Stop G
Sequence Number 1
Notes
Date Text
2007-02-26 14:58:26DENIED
 REFERENCE: FBC-2004 FUEL GAS; CITY OF WEST PALM BEACH
 GAS PERMIT APPLICATION REQUIREMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: PLEASE INDICATE THE BTU LOADS OF THE APPLIANCES
 ON THE RESUBMITTAL.
  
 2. PLEASE INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 NOTE: CLEARLY INDICATE THE DELIVERY PRESSURE ON THE
 RESUBMITTAL. THERE ARE TWO DELIVERY PRESSURES INDICATED
 ON THE SUBMITTED DRAWINGS, ONE IS 21 LB AND THE OTHER
 IS O.5 PSI, PLEASE CLARIFY ON THE RESUBMITTAL WITH ONLY
 INDICATING ONE DELVERY PRESSURE.
  
 3. PLEASE CLEARLY INDICATE ON THE RESUBMITTAL IF THE
 GAS PIPING IS ABOVE GROUND OR UNDERGROUND, AND WHAT GAS
 PIPING IS EXISTING OR NEW.
  
 ******IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved