2007-08-21 19:01:58 
  
 DENIED
  
 1)PLEASE HAVE RAR SIGN AND SEAL THE ROOFING
 CALCULATIONS THAT WERE PROVIDED. ALSO HAVE THE NOA #
 CHANGED TO MATCH THE NEW PRODUCT APPROVAL REQUIRED IN
 COMMENT #2.
  
 2)THE STATE HAS NOT UPDATED THE PRODUCT APPROVAL FOR
 TAMKO MODIFIED ROOFING SYSTEMS AND THE NOA HAS EXPIRED,
 PLEASE PROVIDE 2 COPIES OF THE REVISED MIAMI-DADE
 REPORT # 07-0111.03 THE PAGES 6 & 7 OF 19 ARE THE SAME
 SYSTEM THAT WAS SUBMITTED ON THE OLD PRODUCT APPROVALS.
 THE MIAMI-DADE REPORT WILL THEN BE GIVEN LOCAL PRODUCT
 APPROVAL FOR USE.
  
 3)PER 713.13(2) F.S. IF THE IMPROVEMENT DESCRIBED IN
 THE NOC HAS NOT COMMENCED WITHIN 90 DAYS OF RECORDING,
 THE NOTICE IS VOID
  
 4)THE COPIES OF THE TRUSS ENGINEERING WERE NOT
 RESUBMITTED, THEY ARE NOT REQUIRED BEFORE A PERMIT IS
 ISSUED BUT ARE REQUIRED BEFORE TRUSSES ARE SET.
  
 5)OLD DRAWINGS CAN BE REMOVED FOR RESUBMITTAL BUT BE
 SURE TO INSERT PAGES WITH THE IMPACT FEE STAMP ON THEM
  
 BLDG PLAN REVIEW