Plan Review Notes
Plan Review Notes For Permit 07020467
Permit Number 07020467
Review Stop G
Sequence Number 2
Notes
Date Text
2007-06-20 11:02:40****************PROVISO****************
 GAS SYSTEM PER FBC-2004 FUEL GAS
 TABLES: 402.4(2) AND 402.4(20).
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGS
 REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 4,000 CUBIC FEET REQUIRED.
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  