Plan Review Notes
Plan Review Notes For Permit 07020467
Permit Number 07020467
Review Stop B
Sequence Number 2
Notes
Date Text
2007-06-23 14:14:40 
  
 DENIED
  
 THE FOLLOWING REVIEW COMMENTS WERE NOT COMPLETELY
 ADDRESSED:
  
 5)PROVIDE 2 COPIES OF CURRENT SURVEY SHOWING PROPOSED
 WORK AND ALL REQUIRED SETBACKS. ****NOTE SURVEY AND
 SITE PLAN DO NOT MATCH SEE ZONING REVIEW COMMENTS****
  
 6)SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL. ****REQUIRES CORRECTIONS SEE MECHANICAL
 REVIEW COMMENTS, ALSO CLARIFY R11 ON ENERGY CALC'S AND
 R4.7 ON DRAWINGS****
  
 9)THE FOLLOWING STRUCTURAL DETAILS REQUIRE
 CORRECTION;
 B) PLAN S-2 THE SECTIONS LABELED A/S7 SHOULD BE THE
 TYPICAL TRUSS BEARING DETAIL A/S6. ****NOT
 CORRECTED****
 E) PROVIDE SCHEDULE FOR PRE CAST LINTEL THAT WILL BE
 USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC.
 ****NOA # ON SCHEDULE IS OLD PLEASE USE THE REVISED #
 FROM PRODUCT APPROVALS****
  
 15)THE FOLLOWING CORRECTION ARE REQUIRED FOR THE
 PRODUCT APPROVALS:
 B) PROVIDE THE ROOF SYSTEM FROM THE MODIFIED PRODUCT
 APPROVAL THAT WILL BE USED. *****PROVIDE CALCULATIONS
 FROM RAS 117 PER LIMITATION #7 OF THE NOA, PLEASE NOTE
 THAT NOA USES 12" O/C AT THE 4" LAP AND 2 ROWS AT 12"
 O/C IN MIDDLE. SEEMS EXTREME AT 4" O/C EACH WAY WITH 3"
 PLATES****
  
 NEW
  
 1)TRUSS ENGINEERING IS INCOMPLETE, PROVIDE INDIVIDUAL
 TRUSSES WITH UPLIFT VALUES AT CONNECTION POINTS, THESE
 DO NOT REQUIRE INDIVIDUAL SIGN AND SEAL AS LONG AS
 THERE IS A SIGNED AND SEALED COVER PAGE THAT LISTS THE
 PAGES. ALSO THE WIND DESIGN IS INCORRECT AND DOES NOT
 MATCH THE ARCHITECTURAL AND STRUCTURAL DRAWINGS AND TOP
 AND BOTTOM DEAD LOADS SHALL ALSO MATCH STRUCTURAL
 DRAWINGS.
  
 2)REMOVE MULLION PRODUCT APPROVALS AS NONE ARE SHOWN
 ON THE DRAWINGS. WINDOWS 2A & 2B AND 2L & 2M SHOW
 STRUCTURAL STEEL BETWEEN AND DO NOT REQUIRE MULLIONS.
  
 3)PROVIDE INDIVIDUAL WINDOW DESIGN PRESSURES, IF WE
 USE THE CHART FOR THIS ON S/8, PLAN REVIEW DOES NOT
 INTERPOLATE THEREFORE THE CASEMENT WINDOWS 5050 THAT
 ARE IN THE END ZONE WILL NOT MEET THE DESIGN PRESSURE
 OR A STRONGER GLAZING TYPE MUST BE USED FROM THE
 CHOICES IN THE PRODUCT APPROVAL.
  
 4)PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID, PLEASE RE-RECORD THIS CAN BE DONE AT TIME OF
 FINAL PERMIT PICKUP
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  