Plan Review Notes
Plan Review Notes For Permit 07020467
Permit Number 07020467
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-12 09:19:03DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. A} SHEET P-1 KEY NOTE #6 INDICATES A 3" SANITARY
 RISER.
 B} SHEET P-2 KEY NOTE #1 INDICATES A 4" SANITARY
 DOWN.
 C} SHEET P-3 UNDERGROUND TO 2ND FLOOR RISER BEHIND
 1ST FLOOR LAUNDRY INDICATES A 3" SANITARY RISER. PLEASE
 CORRELATE SHEETS FOR RESUBMITTAL.
  
 2. SHEET P-4 ISOMETRIC WATER RISER DIAGRAM PLEASE ADD
 WATER HAMMER ARRESTORS AT THE TWO DISHWASHERS HOT WATER
 SUPPLY PIPES PER FBC-2004 PLUMBING, SECTION 604.9,
 WATER HAMMER ARRESTORS REQUIRED ON QUICK CLOSING
 VALVES. PLEASE ADJUST PLUMBING GENERAL NOTES #16 TO
 REFLECT THIS ON THE RESUBMITTAL.
  
 3. SHEET P-1 KEY NOTE #2 INDICATES UNDERGROUND WATER
 SUPPLY PIPE TO BE 1" GALVANIZED BUT SHEET P-5 PLUMBING
 GENERAL NOTES #11 INDICATES ALL UNDERGROUND WATER TO BE
 TYPE K COPPER. IS IT THE INTENT TO HAVE KEY NOTES OVER
 RIDE GENERAL NOTES. PLEASE CLARIFY OR CORRELATE ON THE
 RESUBMITTAL.
  
 4. SHEET P-3 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 INDICATE THE CLEANOUT FOR THE WASHING MACHINE AT FOUR
 FEET ABOVE FINNISH FLOOR (4' A.F.F.) PER FBC-2004
 PLUMBING SECTION, 708.7 MINIMUM SIZE AND 708.9 ACCESS.
  
 5. SHEET P-3 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE THE CLEANOUT AT THE JUNCTION OF THE BUILDING
 DRAIN AND BUILDING SEWER AS BEING A TWO-WAY CLEANOUT
 PER FBC-2004 PLUMBING, SECTION 708.3.5 ON THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  