Date |
Text |
2007-03-12 09:52:54 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS; THE CITY OF WEST PALM |
| BEACH GAS PERMIT APPLICATION REQUIREMENTS; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: NOT ALL |
| CORRESPONDING LENGTHS ARE INDICATED. THE LONGEST LENGTH |
| IS BEING INDICATED IS 88' BUT THE ADDED SUM OF THE |
| INDICATED CORRESPONDING LENGTHS EQUALS 77'-6". PLEASE |
| CORRECT AND CORRELATE ON THE RESUBMITTAL. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE ONLY |
| INDICATED PIPING MATERIAL BEING USED IS PE FOR THE |
| UNDERGROUND. ALL PIPING MATERIALS MUST BE INDICATED ON |
| THE RESUBMITTAL. IF THE GAS TYPE IS NATURAL GAS WITH A |
| DELIVERY PRESSURE OF 0.5 PSI PLEASE NOTE THE RED LINE |
| CORRECTIONS TO THE GAS PIPE SIZES. PLEASE REFERENCE THE |
| ATTACHED GAS SIZING TABLES TO THE GAS COMMENTS |
| INDICATING THIS. PLEASE CORRECT AND RESUBMIT. |
| |
| 3. SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TYPE OF |
| GAS BEING USED SHALL BE CLEARLY INDICATED AS, (LP) OR |
| (NATURAL). PLEASE CORRECT ON THE RESUBMITTAL. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: SHEET P-3 GAS ISOMETRIC RISER DIAGRAM: THE TOTAL |
| BTU'S ARE NOT CLEARLY INDICATED AND ARE BEING INDICATED |
| WRONG AS 3?0,000. THE TOTAL SUM OF THE BTU'S SHOULD BE |
| 410,000. PLEASE CORRECT ON THE RESUBMITTAL. |
| ********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |