2007-03-04 17:58:43 | |
| ** UNSAT ** |
| |
| 1) NOTE: 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION |
| HAS BEEN SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH |
| PLACES PROJECTS UNDER THE NEW CODES ADOPTED BY THE |
| STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 (DONE) |
| 2003 NFPA-101(DONE) |
| |
| 2) NOTE: PLEASE SEE LOAD CALCULATIONS AS THERE ARE |
| SEVERAL CODE SECTIONS REFLECTED FROM THE 2002 CODE |
| WHICH ARE NO LONGER ACCURATE. |
| |
| 3) NOTE: PLEASE CORRELATE ALL OF THE SMALL APPLIANCE |
| CIRCUITS AND THE CIRCUITS OF THE LIKE WHICH ARE |
| REQUIRED TO BE FIGURED INTO THE LOAD CALCULATIONS. |
| PLEASE SEE 210.52B1, 210.11C1, AND 220.52A. |
| PLEASE SEE PLANS INDICATE MORE THAN THE FOUR FIGURED |
| AND SHOWN. |
| |
| 4) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE |
| PLANS INDICATE PANEL *B* AS BEING ON THE GROUND FLOOR, |
| YET THE RISER SHOWS PANEL *B* UPSTAIRS AND COORDINATE |
| WITH PANEL *C*. |
| |
| 5) NOTE: PLEASE CORRELATE THE FOLLOWING. |
| PLEASE CORRELATE PANEL *B* AS PANEL *B* ON RISER SHOWS |
| THIS AS 100AMPS AND PANEL *B* SCHEDULE SHOWS THIS AS |
| 150AMPS. |
| PLEASE SEE RISER AND PANEL SCHEDULE FOR THE SAME FOR |
| PANEL *C*. |
| PLEASE SEE RISER AND PANEL SCHEDULE FOR PANEL *A* WHICH |
| SHOWS ONE AS 400A MLO AND THE OTHER AS 300A MLO. PLEASE |
| CORRELATE ALL OF THE ABOVE. |
| FBC 106.1.2 , 106.3.5.4 |
| |
| 6) NOTE: PLEASE CORRELATE LOAD FOR DISHWASHER(S) ON |
| LOAD CALCULATIONS AND THE LOAD AS SHOWN ON PANEL |
| SCHEDULE. PLEASE SEE THE AMPERAGE AS SHOWN ON PANEL |
| DOES NOT FIGURE FOR THE LOAD IN KVA AS SHOWN IN |
| CALCULATIONS. |
| 220. |
| FBC 106.3.5.4 |
| |
| 7) NOTE: PLEASE SEE THE LOAD FOR THE DISPOSAL WHICH |
| ALSO DOES NOT CORRELATE WITH THE VA ON LOAD |
| CALCULATIONS AS LOAD ON PANEL SCHEDULE ONLY SHOWS 1AMP |
| LOAD? |
| 220. |
| FBC 106.3.5.4 |
| |
| 8) NOTE: PLEASE SEE RISER FOR GROUNDING ELECTRODE |
| SYSTEM SHOWS ATTACHMENT TO *BLDG STEEL* WHICH IS OK AND |
| REQUIRED IF * BLDG STEEL* IS PRESENT. PLEASE INCLUDE |
| *FOOTER STEEL* AS REQUIRED PER 250.50. |
| |
| 9) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE |
| SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS |
| SMOKE DETECTORS. |
| PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN |
| SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY |
| INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS |
| ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN |
| THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS |
| OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE |
| ALARMS. |
| THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY |
| THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| FOR OTHER NEW HOMES. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE*. |
| PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| |
| 10) NOTE: PLEASE KNOW THAT IN NO CASE MAY *STICKERS* OF |
| ANY KIND BE PLACED ON PLANS. |
| PLEASE REVISE PLANS TO CORRECT THE ISSUE AS TO WHY THE |
| LABELS WERE PLACED ON SHEETS. |
| 106.3.1 ADMIN SECTION. |
| FS 471.025 |
| |
| 11) NOTE: PLEASE SEE THAT THE RECESSED LIGHTING IN THE |
| NUMBER AS SHOWN ON PLANS MUST BE BASED ON THE NUMBER OF |
| FIXTURES AND MAXIMUM WATTAGE PER FIXTURE. PLEASE SEE |
| THE PREVIOUS CODE 2002 WHICH IS SECTION 220.3B4. PLEASE |
| SEE 220.14/220.12. |
| PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION |
| MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A |
| CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER |
| FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN |
| ADDITION TO THE GENERAL LIGHTING LOADS FIGURED. |
| |
| 12) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED |
| LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4. |
| THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED |
| SPACE ETC. |
| |
| 13 NOTE: PLEASE SEE THAT THE TRUSS PLANS AND |
| ENGINEERINF CONTAINS A *RUBBER STAMP* INSTEAD OF THE |
| REQUIRED ORIGINAL SIGNATURE FROM THE ENGINEER OF RECORD |
| AS SHOWN. THIS IS REQUIRED PER FAC 61G15-23.002 AND FS |
| 471.025 |
| THIS IS ALSO REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| OTHER TRADE(S). |
| THIS COMMENT IS NOT FOR THE DEISGNER OF THE ELECTRICAL |
| PLANS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |