Plan Review Notes
Plan Review Notes For Permit 07020467
Permit Number 07020467
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-04 17:58:43 
 ** UNSAT **
  
 1) NOTE: 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION
 HAS BEEN SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH
 PLACES PROJECTS UNDER THE NEW CODES ADOPTED BY THE
 STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72 (DONE)
 2003 NFPA-101(DONE)
  
 2) NOTE: PLEASE SEE LOAD CALCULATIONS AS THERE ARE
 SEVERAL CODE SECTIONS REFLECTED FROM THE 2002 CODE
 WHICH ARE NO LONGER ACCURATE.
  
 3) NOTE: PLEASE CORRELATE ALL OF THE SMALL APPLIANCE
 CIRCUITS AND THE CIRCUITS OF THE LIKE WHICH ARE
 REQUIRED TO BE FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE SEE 210.52B1, 210.11C1, AND 220.52A.
 PLEASE SEE PLANS INDICATE MORE THAN THE FOUR FIGURED
 AND SHOWN.
  
 4) NOTE: PLEASE CORRELATE RISER AND PLANS. PLEASE SEE
 PLANS INDICATE PANEL *B* AS BEING ON THE GROUND FLOOR,
 YET THE RISER SHOWS PANEL *B* UPSTAIRS AND COORDINATE
 WITH PANEL *C*.
  
 5) NOTE: PLEASE CORRELATE THE FOLLOWING.
 PLEASE CORRELATE PANEL *B* AS PANEL *B* ON RISER SHOWS
 THIS AS 100AMPS AND PANEL *B* SCHEDULE SHOWS THIS AS
 150AMPS.
 PLEASE SEE RISER AND PANEL SCHEDULE FOR THE SAME FOR
 PANEL *C*.
 PLEASE SEE RISER AND PANEL SCHEDULE FOR PANEL *A* WHICH
 SHOWS ONE AS 400A MLO AND THE OTHER AS 300A MLO. PLEASE
 CORRELATE ALL OF THE ABOVE.
 FBC 106.1.2 , 106.3.5.4
  
 6) NOTE: PLEASE CORRELATE LOAD FOR DISHWASHER(S) ON
 LOAD CALCULATIONS AND THE LOAD AS SHOWN ON PANEL
 SCHEDULE. PLEASE SEE THE AMPERAGE AS SHOWN ON PANEL
 DOES NOT FIGURE FOR THE LOAD IN KVA AS SHOWN IN
 CALCULATIONS.
 220.
 FBC 106.3.5.4
  
 7) NOTE: PLEASE SEE THE LOAD FOR THE DISPOSAL WHICH
 ALSO DOES NOT CORRELATE WITH THE VA ON LOAD
 CALCULATIONS AS LOAD ON PANEL SCHEDULE ONLY SHOWS 1AMP
 LOAD?
 220.
 FBC 106.3.5.4
  
 8) NOTE: PLEASE SEE RISER FOR GROUNDING ELECTRODE
 SYSTEM SHOWS ATTACHMENT TO *BLDG STEEL* WHICH IS OK AND
 REQUIRED IF * BLDG STEEL* IS PRESENT. PLEASE INCLUDE
 *FOOTER STEEL* AS REQUIRED PER 250.50.
  
 9) NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE INDICATE
 SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS THESE AS
 SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE WE WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. BY
 THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 10) NOTE: PLEASE KNOW THAT IN NO CASE MAY *STICKERS* OF
 ANY KIND BE PLACED ON PLANS.
 PLEASE REVISE PLANS TO CORRECT THE ISSUE AS TO WHY THE
 LABELS WERE PLACED ON SHEETS.
 106.3.1 ADMIN SECTION.
 FS 471.025
  
 11) NOTE: PLEASE SEE THAT THE RECESSED LIGHTING IN THE
 NUMBER AS SHOWN ON PLANS MUST BE BASED ON THE NUMBER OF
 FIXTURES AND MAXIMUM WATTAGE PER FIXTURE. PLEASE SEE
 THE PREVIOUS CODE 2002 WHICH IS SECTION 220.3B4. PLEASE
 SEE 220.14/220.12.
 PLEASE KNOW THIS WAS CONFIRMED AT THE SOUTHERN SECTION
 MEETING AND BROUGHT FORTH TO THE CODE PANELIST. WHEN A
 CONSIDERABLE NUMBER OF RECESSED FIXTURES OR OTHER
 FIXTURES ARE SHOWN THEN THE LOADS NEED TO BE SHOWN IN
 ADDITION TO THE GENERAL LIGHTING LOADS FIGURED.
  
 12) NOTE: PLEASE BE SURE TO STATE THE TYPE OF RECESSED
 LIGHTING FIXTURE TO BE USED FBC 13-606.1.ABC.1.2.4.
 THIS IS TO ALLEVIATE THE AIR MOVEMENT FROM CONDITIONED
 SPACE ETC.
  
 13 NOTE: PLEASE SEE THAT THE TRUSS PLANS AND
 ENGINEERINF CONTAINS A *RUBBER STAMP* INSTEAD OF THE
 REQUIRED ORIGINAL SIGNATURE FROM THE ENGINEER OF RECORD
 AS SHOWN. THIS IS REQUIRED PER FAC 61G15-23.002 AND FS
 471.025
 THIS IS ALSO REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADE(S).
 THIS COMMENT IS NOT FOR THE DEISGNER OF THE ELECTRICAL
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH