Plan Review Notes
Plan Review Notes For Permit 07020464
Permit Number 07020464
Review Stop P
Sequence Number 2
Notes
Date Text
2007-05-03 13:44:41DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS.
 ** FBC-2004 CHAPTER 1, THE CITY OF WEST PALM BEACH
 AMENDMENTS.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO/OK** PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: THE RESUBMITTED PLANS ARE STILL HARD TO READ. THE
 WORDING IS NOT LEGIBLE DUE TO THE INK RUNNING TOGETHER.
 PLEASE SUBMIT NEW SHEETS THAT ARE LEGIBLE. PLEASE
 REFERENCE ALL CIRCLED AREAS IN RED INK THAT ARE NOT
 LEGIBLE AND PLEASE CORRECT AND RESUBMIT.
  
 2. **NO** PER R4101.6.6.4 THE HAND WRITTEN CHANGES
 MADE FOR THE TWO SUCTION INLETS ON THE PIPING DIAGRAM
 ARE WRONG. THE HAND WRITTEN CHANGES ARE INDICATING A
 THREE FEET CENTER TO CENTER SEPERATION OF THE MAIN
 DRAINS, WHICH IS WRONG. THE CORRECT INDICATION SHOULD
 BE THAT THE TWO SUCTION INLETS PER PUMP SHOULD BE
 SEPERATED A MINIMUM OF THREE FEET. PLEASE CORRECT AND
 RESUBMIT.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 6. **OK**
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721