Plan Review Notes
Plan Review Notes For Permit 07020464
Permit Number 07020464
Review Stop P
Sequence Number 1
Notes
Date Text
2007-04-04 09:58:50DENIED
 REFERENCE:
 ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 NOTE: PLANS ARE HARD TO READ AND THE PIPING SCHEMATIC
 DOES NOT REFLECT THE POOL LAYOUT. PLEASE DELETE THE
 SPA, AND CLEANING LINE FROM THE SCHEMATIC ON THE
 RESUBMITTAL AND CLEARLY INDICATE THAT THESE ITEMS ARE
 NOT BEING USED IN THE "POOL DATA & EQUIPMENT &
 CRITERIA" ON THE RESUBMITTAL.
  
 2. PER R4101.6.6.4 SUCTION INLETS PER PUMP THE TWO
 SUCTION INLETS ON THE PIPING DIAGRAM ARE INDICATED IN
 THE WRONG PLACE. IF IT IS THE INTENT TO LOCATE THE TWO
 SUCTION INLETS IN THE SIDE WALL THEY MUST BE ONE EACH
 ON TWO SEPERATE VERTICAL WALLS. PLEASE REFLECT THIS ON
 THE RESUBMITTAL.
  
 3.FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK.
 NOTE: PLEASE INDICATE ON THE RESUBMITTED POOL EQUIPMENT
 ANCHOR DETAIL THAT THE SLAB IS A NOMINAL 4 INCH THICK
 (4")
  
 4. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC.
 R4101.9 WATER SUPPLY, LOCAL ORD.
 #2853-95, BACKFLOW REQUIRED ON WATER
 SERVICE.(ADD TO NOTES)
  
 5.FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
  
 6.FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.
 (ADD TO NOTES)
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721