2007-04-04 09:58:50 | DENIED |
| REFERENCE: |
| ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004, CHAPTER 1, SECTION |
| 106.1.3, QUALITY OF BUILDING PLANS: THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| NOTE: PLANS ARE HARD TO READ AND THE PIPING SCHEMATIC |
| DOES NOT REFLECT THE POOL LAYOUT. PLEASE DELETE THE |
| SPA, AND CLEANING LINE FROM THE SCHEMATIC ON THE |
| RESUBMITTAL AND CLEARLY INDICATE THAT THESE ITEMS ARE |
| NOT BEING USED IN THE "POOL DATA & EQUIPMENT & |
| CRITERIA" ON THE RESUBMITTAL. |
| |
| 2. PER R4101.6.6.4 SUCTION INLETS PER PUMP THE TWO |
| SUCTION INLETS ON THE PIPING DIAGRAM ARE INDICATED IN |
| THE WRONG PLACE. IF IT IS THE INTENT TO LOCATE THE TWO |
| SUCTION INLETS IN THE SIDE WALL THEY MUST BE ONE EACH |
| ON TWO SEPERATE VERTICAL WALLS. PLEASE REFLECT THIS ON |
| THE RESUBMITTAL. |
| |
| 3.FBC-2004 SEC. 424.2.7.2, OR |
| FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| EQUIPMENT SHALL BE MOUNTED ON A |
| SUBSTANTIAL BASE IN A MANNER THAT WILL |
| ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| BE A NOMINAL 4" THICK. |
| NOTE: PLEASE INDICATE ON THE RESUBMITTED POOL EQUIPMENT |
| ANCHOR DETAIL THAT THE SLAB IS A NOMINAL 4 INCH THICK |
| (4") |
| |
| 4. FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| R4101.9 WATER SUPPLY, LOCAL ORD. |
| #2853-95, BACKFLOW REQUIRED ON WATER |
| SERVICE.(ADD TO NOTES) |
| |
| 5.FBC-2004 SEC. 424.2.14.4, OR |
| FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| ALL WATER HEATING EQUIPMENT SHALL BE |
| INSTALLED WITH FLANGES OR UNION |
| CONNECTIONS ADJACENT TO THE HEATER. |
| (ADD TO NOTES) |
| |
| 6.FBC-2004 SEC. 424.2.14, OR FBCR-2004 |
| SEC. R4101.15 GAS PIPING SHALL COMPLY |
| WITH FBC FUEL GAS.SEPARATE PLANS AND |
| PERMIT REQUIRED. |
| (ADD TO NOTES) |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |