Plan Review Notes
Plan Review Notes For Permit 07020459
Permit Number 07020459
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-11 16:55:25** DENIED REVISION**
  
 1) NOTE: ** PLEASE SEE SOME ITEMS WHICH WERE *REDLINED*
 ON ISSUE PLANS WERE NOT ADDRESSED. THERE WERE SOME
 NOTES CORRECTED.
  
 *** NOTES REDLINED***
 * PLEASE SEE PREVIOUS REQUESTED CODES AND NOTES WERE
 PLACED ON D-1 AND NOT ON ELECTRICAL SHEETS. THIS
 INCLUDES THE NOTES FOR RECESSED LIGHTING REQUIREMENTS
 PER 13-606.1.ABC.1.2.4 AND CORRECT ADOPTED CODES FOR
 DESIGN.( PLEASE PLACE ON ELECTRICAL SHEETS).
 * NOTES ON ELECTRICAL SHEETS IN LEGEND STILL INDICATE
 THE 2002 NEC.
  
 ** PLEASE CORRECT THE ABOVE ALONG WHEN ANY OTHER
 REVISIONS ARE MADE TO PLANS.
  
 2) NOTE: PLEASE SEE AFI PROTECTION IS STILL SHOWN ON
 RECEPTACLES WHEN THIS PROTECTION IS REQUIRED FOR THE
 CIRCUIT.AFCI RECEPTACLE IS NOT MADE, AND ONLY NEEDS
 TO LIST THE CIRCUIT IN THE PANEL.
 210.12
 AS STATED ON PREVIOUS REVIEW IF THERE ARE ANY QUESTIONS
 OR COMMENTS TO PLEASE CALL TO GO OVER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]