Plan Review Notes
Plan Review Notes For Permit 07020459
Permit Number 07020459
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-04 11:56:42DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SITE DRAINAGE PLANS SHOWING COMPLIANCE WITH
 R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. EXTERIOR
 WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) SHALL
 HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE RATING
 WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL NOT
 EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM AN
 ADJACENT PROJECTION OR WALL.
 EXCEPTION : DETACHED GARAGES ACCESSORY TO A DWELLING
 LOCATED WITHIN 2 FEET (610 MM) OF A LOT LINE SHALL BE
 PERMITTED TO HAVE ROOF EAVE PROJECTIONS NOT EXCEEDING 4
 INCHES (102 MM).
 PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 EXCEPTION: TOOL AND STORAGE SHEDS, PLAYHOUSES AND
 SIMILAR STRUCTURES ARE NOT REQUIRED TO PROVIDE WALL
 PROTECTION BASED ON LOCATION ON THE LOT.
  
 4) SHOW COMPLIANCE WITH R302.2 OPENINGS.
 OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF
 A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM
 AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET
 (1828 MM). THIS DISTANCE SHALL BE MEASURED
 PERPENDICULAR TO THE LINE USED TO DETERMINE THE
 SEPARATION DISTANCE.
 EXCEPTIONS:
 1.OPENINGS SHALL BE PERMITTED IN WALLS THAT ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 2.FOUNDATION VENTS INSTALLED IN COMPLIANCE WITH
 THIS CODE ARE PERMITTED.
  
 5) PLEASE CLARIFY THE SCREEN BLOCK THAT IS SPECIFIED ON
 SHEET A1.0 AT THE GARDEN WALL.
  
 6) THE SCREEN BLOCK SPECIFIED AT THE GARAGE IN THE
 GENERAL NOTES ON A2.0 CAN NOT BE LOCATED IN THE FIRE
 RATED ZERO LOT LINE WALL.
  
 7)1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT.
  
 8) SHOW COMPLIANCE WITH G2408.3 (305.5) PRIVATE
 GARAGES.
 APPLIANCES LOCATED IN PRIVATE GARAGES SHALL BE
 INSTALLED WITH A MINIMUM CLEARANCE OF 6 FEET (1829 MM)
 ABOVE THE FLOOR.
 EXCEPTION: THE REQUIREMENTS OF THIS SECTION SHALL NOT
 APPLY WHERE THE APPLIANCES ARE PROTECTED FROM MOTOR
 VEHICLE IMPACT AND INSTALLED IN ACCORDANCE WITH SECTION
 G2408.2.
  
 9) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE
 GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS
 ATTIC AREA BY NOT LESS THAN ? -INCH (12.7 MM) GYPSUM
 BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH
 HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE
 ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE
 X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 ?-INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT.
  
 10) SPECIFY THE SIZE OF THE ATTIC ACCESS ON THE
 PLANS.R807.1 ATTIC ACCESS .
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING. SEE SECTION M1305.1.3
 FOR ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 11) PLEASE CLARIFY THE COLUMN SHOWN ON A1.0 AT THE
 CORNER OF THE BREAKFAST ROOM WHICH APPEARS TO HAVE 4
 VERTICAL REBARS AND IS LABELED AS A TYPE 2 COLUMN.
  
 12) THE TAG FOR SECTION 8/A1.0 AT THE FAMILY ROOM WALL
 IS IN THE WRONG LOCATION. IT SHOULD BE AT THE DOOR
 OPENING.
  
 13) SLIDING GLASS DOOR B IS SHOWN ON THE SCHEDULE ON
 A2.0 AS TWELVE FEET WIDE AND UNDER REMARKS IN SAME
 SCHEDULE IT IS SPECIFIED AS A 16080. PLEASE CORRECT.
 ALSO THE TRANSOM ABOVE IS SPECIFIED AS TWO 96" X 24"
 WINDOWS IN THE SCHEDULE ON A2.0. PLEASE CORRECT.
  
 14) PLEASE SPECIFY THE 8 X 8 LINTEL BETWEEN THE 12'
 SLIDING GLASS DOOR AND THE FIXED GLASS TRANSOM AT THE
 BREAKFAST ROOM.THE LINTEL SCHEDULE AND ROOF/LINTEL
 PLAN ON A5.0 DOES NOT SPECIFY THIS LINTEL.
  
 15) PROVIDE A FRAMING PLAN FOR THE ARCH OPENINGS.
  
 16)ON SHEET A2.0 A 96" X 24" FIXED WINDOW IS
 SPECIFIED ABOVE THE THE 6' WIDE SLIDING GLASS DOOR AT
 THE DINING ROOM. HOWEVER, IT IS NOT SHOWN ON THE
 ELEVATION ON A4.0.
  
 17) THE WINDLOAD PRESSURES FOR THE TWO SIDE SWING DOORS
 AT THE COVERED TERRACE ARE NOT SPECIFIED ON SHEET
 A4.0.
  
 18) THE WINDLOAD PRESSURES ARE NOT SPECIFIED FOR THE
 OVAL LAUNDRY ROOM WINDOW OR THE EXTERIOR DOOR TO
 BEDROOM #3.THE PRESSURES SPECIFIED FOR THE WINDOW IN
 BEDROOM #2 ON THE RIGHT ELEVATION ARE DIFFERENT FROM
 THE ONES FOR THE SAME WINDOW ON THE FRONT ELEVATION.
 SEE SHEET A4.0.
  
 19) SUBMIT THE GLASS BLOCK MANUFACTURER'S
 SPECIFICATIONS FOR THE INSTALLATION OF THE ONE HOUR
 FIRE RATED GLASS BLOCK.
  
 20) SUBMIT THE SIMPSON TECHNICAL BULLETINS THAT ALLOW
 THE HUS 26 AND HGUS 28-2 HANGERS TO BE FASTENED TO
 MASONRY OR CONCRETE WITH CONCRETE SCREWS.
  
 21) SUBMIT THE NOA FOR THE 8" WIDE LINTELS, WHICH ARE
 NOT INCLUDED IN THE NOA THAT WAS SUBMITTED.
  
 22) THE PRODUCT APPROVAL SUBMITTED FOR THE 12' WIDE SGD
 IS FOR 4 OR 2 PANEL DOORS, THE PLAN SHOWS A 3 PANEL
 DOOR. PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  