2007-04-14 13:47:08 | |
| |
| DENIED |
| |
| 1)DRAWINGS TO COMPLY WITH THE LATEST CODE, PLACE NOTE |
| ON PLANS THAT THEY CONFORM TO THE 2004 FLORIDA BUILDING |
| CODE WITH 2006 REVISIONS |
| |
| 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| BUILDING PER 1603.1.4 FBC |
| |
| 3)PROVIDE TYPE OF CONSTRUCTION AND OCCUPANCY GROUP ON |
| PLANS |
| |
| 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| PER 108.3 FBC*.VALUE ADJUSTED TO $307,520 WHICH |
| INCREASES THE PERMIT FEE. BALANCE DUE IS $105.43 |
| |
| 5)PLAN, ELEVATION AND DOOR, WINDOW SCHEDULE DO NOT |
| MATCH. WINDOW 1,HAS QUANTITY OF ONE, SHOULD BE THREE. |
| IS THERE A PICTURE WINDOW ABOVE THE SGD "A" |
| IF SO IS LINTEL BETWEEN OR MULLION AND WHAT IS THE |
| DESIGN PRESSURE. |
| |
| 6)BUILDING ELEVATION TO INCLUDE MEAN ROOF HEIGHT |
| |
| 7)SUBMIT ENGINEERED TRUSS DRAWINGS THAT |
| COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR |
| BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND |
| APPROVED BY THE DESIGNER OF RECORD |
| |
| 8)PROVIDE NOTE FOR SHOWER DOORS TO BE SAFETY GLAZING |
| PER R308.4 FBC RES. |
| |
| 9)IF WOOD BUCKS ARE TO BE USED AN ATTACHMENT DETAIL |
| IS REQUIRED FOR THE TRANSFER OF APPLICABLE LOADS TO THE |
| BUILDING PER R613.6.1.1 FBC RES. |
| AS THE PRODUCT APPROVALS DO NOT SPECIFY ANY ATTACHMENT |
| METHOD |
| |
| 10)NOA FOR PRE-CAST LINTELS IS INCORRECT SUBMITTED |
| NOA IS FOR 4,6 AND 12" WIDE BLOCK APPLICATIONS PROVIDE |
| MIAMI-DADE NOA # 03-0605.05 FOR 8" LINTELS |
| |
| 11)SEVERAL LINTEL LENGTHS ARE TO SHORT TO MEET THE |
| MINIMUM END BEARING OF 4" PER 2104.1.5 FBC. THE |
| FOLLOWING NEED CORRECTION |
| A) LINTEL #7 FOR SGD "A" |
| B) LINTEL #3 FOR GARAGE DOOR "F AND SGD "C" |
| C) LINTEL #6 FOR WINDOW #7 |
| |
| 12)GLASS BLOCK MEETS THE DESIGN PRESSURES REQUIRED |
| BUT IS ONLY SMALL MISSILE IMPACT RATED. PER 1609.1.4 |
| FBC GLAZING WITHIN THE FIRST 30 FEET FROM GRADE ARE |
| REQUIRED TO MEET LARGE MISSILE IMPACT TEST REQUIREMENTS |
| THEREFORE THESE OPENINGS WILL REQUIRE AN IMPACT |
| PROTECTION SYSTEM. |
| |
| 13)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT IS REQUIRED PRIOR TO |
| A PERMIT BEING ISSUED |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |