Plan Review Notes
Plan Review Notes For Permit 07020455
Permit Number 07020455
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-28 14:25:50 
 PLANS EXAMINER : KEN CONRAD
 PROJECT: 1201 SOUTH FLAGLER DRIVE
  
 NOTE: REQUIRE A PRELIMINARY INSPECTION AS PER FBC
 109.2. BEFORE ISSUING A PERMIT, THE BUILDING OFFICIAL
 IS AUTHORIZED TO EXAMINE OR CAUSE TO BE EXAMINED
 BUILDINGS, STRUCTURES AND SITES FOR WHICH AN
 APPLICATION HAS BEEN FILED.
  
  
 A) FOR NEW CONSTRUCTION REPAIR/PERMITTED MATERIALS:
 FEBC SECTION 401.2 EXCEPT AS OTHERWISE REQUIRED HEREIN,
 WORK SHALL BE DONE USING MATERIALS PERMITTED BY THE
 APPLICABLE CODE FOR NEW CONSTRUCTION OR USING LIKE
 MATERIALS SUCH THAT NO HAZARD TO LIFE, HEALTH AND
 PROPERTY IS CREATED.
  
 B)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 C) FEBC 401.3 THE WORK SHALL NOT MAKE THE BUILDING LESS
 CONFORMING TO THE BUILDING, PLUMBING,
 ELECTRICAL,MECHANICAL OR FIRE CODES OF THE
 JURISDICTION, OR TO ALTERNATIVE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION, OR ANY PREVIOUSLY APPROVED
 PLANS , MODIFICATIONS, ALTERNATIVE METHODS, OR
 COMPLIANCE ALTERNATIVES, THAN IT WAS BEFORE THE REPAIR
 WAS UNDERTAKEN.
  
 D) FEBC 404.1 REPAIRS SHALL BE DONE IN A MANNER THAT
 MAINTAINS THE LEVEL OF FIRE PROTECTION PROVIDED.
  
 E) FEBC 405.1 GENERAL. REPAIRS SHALL BE DONE IN A
 MANNER THAT MAINTAINS THE LEVEL OF PROTECTION PROVIDED
 FOR THE MEANS OF EGRESS.
  
 F) FEBC 406.1 GENERAL. REPAIRS SHALL BE DONE IN
 ACCORDANCE WITH CHAPTER 11 OF THE FBC ACCESSIBILITY
 SECTION.
  
 G) FEBC 407.2 REDUCTION OF STRENGTH. REPAIRS SHALL NOT
 REDUCE THE STRUCTURAL STRENGTH OR STABILITY OF THE
 BUILDING, STRUCTURE OR ANY INDIVIDUAL MEMBER THEREOF.
  
 H) FEBC 407.3.1 NEW STRUCTURAL FRAME MEMBERS. NEW
 STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF DAMAGED
 BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE.
  
 PLANS EXAMINER : KEN CONRAD
 PROJECT: 1201 SOUTH FLAGLER DRIVE
  
 NOTE: REQUIRE A PRELIMINARY INSPECTION AS PER FBC
 109.2. BEFORE ISSUING A PERMIT, THE BUILDING OFFICIAL
 IS AUTHORIZED TO EXAMINE OR CAUSE TO BE EXAMINED
 BUILDINGS, STRUCTURES AND SITES FOR WHICH AN
 APPLICATION HAS BEEN FILED.
  
  
 A) FOR NEW CONSTRUCTION REPAIR/PERMITTED MATERIALS:
 FEBC SECTION 401.2 EXCEPT AS OTHERWISE REQUIRED HEREIN,
 WORK SHALL BE DONE USING MATERIALS PERMITTED BY THE
 APPLICABLE CODE FOR NEW CONSTRUCTION OR USING LIKE
 MATERIALS SUCH THAT NO HAZARD TO LIFE, HEALTH AND
 PROPERTY IS CREATED.
  
 B)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 C) FEBC 401.3 THE WORK SHALL NOT MAKE THE BUILDING LESS
 CONFORMING TO THE BUILDING, PLUMBING,
 ELECTRICAL,MECHANICAL OR FIRE CODES OF THE
 JURISDICTION, OR TO ALTERNATIVE MATERIALS, DESIGN AND
 METHODS OF CONSTRUCTION, OR ANY PREVIOUSLY APPROVED
 PLANS , MODIFICATIONS, ALTERNATIVE METHODS, OR
 COMPLIANCE ALTERNATIVES, THAN IT WAS BEFORE THE REPAIR
 WAS UNDERTAKEN.
  
 D) FEBC 404.1 REPAIRS SHALL BE DONE IN A MANNER THAT
 MAINTAINS THE LEVEL OF FIRE PROTECTION PROVIDED.
  
 E) FEBC 405.1 GENERAL. REPAIRS SHALL BE DONE IN A
 MANNER THAT MAINTAINS THE LEVEL OF PROTECTION PROVIDED
 FOR THE MEANS OF EGRESS.
  
 F) FEBC 406.1 GENERAL. REPAIRS SHALL BE DONE IN
 ACCORDANCE WITH CHAPTER 11 OF THE FBC ACCESSIBILITY
 SECTION.
  
 G) FEBC 407.2 REDUCTION OF STRENGTH. REPAIRS SHALL NOT
 REDUCE THE STRUCTURAL STRENGTH OR STABILITY OF THE
 BUILDING, STRUCTURE OR ANY INDIVIDUAL MEMBER THEREOF.
  
 H) FEBC 407.3.1 NEW STRUCTURAL FRAME MEMBERS. NEW
 STRUCTURAL FRAME MEMBERS USED IN THE REPAIR OF DAMAGED
 BUILDINGS, INCLUDING ANCHORAGE AND CONNECTIONS, SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE.
  
 I) FEBC 407.3.4 OTHER UNCOVERED STRUCTURAL ELEMENTS.
 WHERE IN THE COURSE OF CONDUCTING REPAIRS OTHER
 UNCOVERED STRUCTURAL ELEMENTS ARE FOUND TO BE UNSOUND
 OR OTHERWISE STRUCTURALLY DEFICIENT, SUCH ELEMENTS
 SHALL BE MADE TO CONFORM TO THE REQUIREMENTS OF
 407.3.2.1.1 OF THE EXISTING BUILDING CODE.
  
 J) THE NEWLY REPAIRED WALLS SHALL CONFORM TO THE
 REQUIREMENTS OF FBC 1403.2, WEATHER PROTECTION.
 EXTERIOR WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER RESISITANT EXTERIOR WALL ENVELOPE. THE EXTERIOR
 WALL ENVELOPE SHALL INCLUDE FLASHING, AS DESCRIBED IN
 SECTION 1405.3. THE EXTERIOR WALL ENVELOPE SHALL BE
 DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT
 THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY
 PROVIDING A WATER RESISTIVE BARRIER BEHIND THE EXTERIOR
 VENEER AS DESCRIBED IN SECTION 1404.2 AND A MEANS FOR
 DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE EXTERIOR
 OF THE VENEER, UNLESS IT HAS BEEN DETERMINED THAT THE
 PENETRATION OF THE WATER BEHIND THE VENEER SHALL NOT BE
 DETRIMENTAL TO THE BUILDING PERFORMANCE. ALL EXTERIOR
 FINISHES SHALL BE APPLIED IN ACCORDANCE WITH THE
 MANUFACTURE'S SPECIFICATIONS OF INSTALATION
 INSTRUCTIONS. PROTECTION AGAINST CONDENSATION IN THE
 EXTERIOR WALL ASSEMBLY SHALL BE PROVIDED IN ACCORDANCE
 WITH CHAPTER 13 OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 K) ALL NEWLY INSTALLED BRICK SHALL CONFORM TO ASTM C55
 AS PER FBC 2103.1.
  
 L) AS PER FBC 2103.11.5, MORTAR SHALL CONFORM TO ASTM
 C-270.
  
 M) REQUIRE AN ON-SITE ENGINEER TO MONITOR WORK
 IN-PROGRESS AND PROVIDE CERTIFICATE OF COMPLIANCE AS
 PER FBC 105.14 DUE TO THE COMPLEXITY OF THE REPAIR.
  
 N) REQUIRE CONCRETE RESTORATION REPAIR DETAILS FOR THE
 BALCONIES PREPARED BY A LICENSED PROFESSIONAL ENGINEER.
 SUBMIT ALL PRODUCT APPROVALS AND/OR MANUFACTURER'S
 SPECIFICATIONS.
  
 O) SEPARATE MECHANICAL, ELECTRICAL AND PLUMBING PERMITS
 MAY BE REQUIRED.