2007-03-20 11:30:10 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FACFLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)BUILDING INFORMATION, ITEM 3, CONSTRUCTION TYPE |
| SHOULD INCLUDE A OR B, FBC 6, NOT "PROTECTED". |
| |
| 2.)BUILDING INFORMATION, ITEM 3, STATES THAT THIS IS |
| "PROTECTED".INCLUDE FIRE RESISTANCE RATING |
| REQUIREMENTS. |
| |
| 3.)BUILDING INFORMATION, ITEM 5, STATES THAT THIS IS |
| A 2 STORY EXISTING, BUILDING, THE SITE PLAN SHOWS A 1 |
| STORY BUILDING. |
| |
| 4.)DECLARE BUILDING HEIGHT. |
| |
| 5.)ITEM 9 E STATES SEE WINDOW & DOOR SCHEDULE; NO |
| SCHEDULE WAS INCLUDED.THE DESIGN PRESSURES ARE |
| DECLARED IN TWO DIFFERENT PLACES, NEITHER OF WHICH IS A |
| WINDOW/DOOR SCHEDULE. |
| |
| 6.)THE WINDOW WALL SYSTEM NOTES STATES "THE BOD IS |
| BASED ON . . . "WHAT IS BOD? |
| |
| 7.)ASTM C936-82, SOLID CONCRETE INTERLOCKING PAVING |
| UNITS, IS IN THE PACKAGE.THE PURPOSE OF THIS IS NOT |
| CLEAR.THIS IS AN OUTDATED STANDARD, 15 YEARS OLD. C1, |
| SOMEONE HAS WRITTEN THAT PAVING IS NOT IN THIS |
| CONTRACT. |
| |
| 8.)THE APPLICAITON STATES THAT YOU ARE "REMOVING REAR |
| WINDOWS AND BLOCKING THEM UP."SHOW THIS ON THE PLAN, |
| PROVIDE A DETAIL.REQUIRED FIRE RESISTANCE IS TO BE |
| MAINTAINED; ALL REQUIREMENTS ARE TO BE SHOWN ON THE |
| PLAN AND DETAILS ARE TO BE EITHER A TESTED ASSEMBLY OR |
| CALCULATED FIRE RESISTANCE FBC9. |
| |
| 9.)THE PLAN STATES THAT YOU ARE ADDING ONE REAR DOOR. |
| PROVIDE A PRODUCT APPROVAL FOR THE DOOR.PROVIDE A |
| DETAIL. |
| |
| 10.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 11.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD, FBC*106.3.3. |
| |
| 12.)A1 NOTES THAT BAHAMA SHUTTERS ARE TO BE INSTALLED |
| ON EACH NEW DOOR AND WINDOW.HOW FAR INTO THE PATH OF |
| TRAVEL WILL THIS SHUTTER EXTEND?SHOW THE LINE OF THE |
| BAHAMA SHUTTER AND SIDEWALK ON THE SITE PLAN.SHOW THE |
| SHUTTERS ON THE ELEVATIONS. |
| |
| 13.)THE WINDOW NOTES STATE THAT -176 PSF IS REQUIRED |
| FOR THE STOREFRONT, ELEVATIONS REQUIRE -36.4.WHERE |
| THERE IS A CONFLICT, THE MOST STRINGENT WILL APPLY. |
| THE PRODUCT APPROVAL SUBMITTED ARE NOT COMPLIANT WITH |
| THIS DESIGN PRESSURE REQUIREMENT (-176PSF). |
| |
| 14.)THE APPLICATON STATES "REMOVING ALL REAR WINDOWS |
| AND BLOCKING THEM UP."THE NEW REAR ELEVATION A1 SHOWS |
| THE EXISTING WINDOWS.PERMIT APPLICATION SHOULD BE |
| CONSISTENT WITH THE PLAN AND THE SCOPE OF WORK. |
| |
| 15.)THE NEW SOUTH ELEVATION SHOWS NEW FIXED GLASS AND |
| A RECTANGLE AROUND THE WINDOW.WHAT IS THIS?THE |
| OPENING APPEARS LARGER.PROVIDE DETAILS AND CLARIFY |
| SCOPE OF WORK. |
| |