Plan Review Notes
Plan Review Notes For Permit 07020441
Permit Number 07020441
Review Stop P
Sequence Number 3
Notes
Date Text
2007-08-30 15:19:03DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 ******FROM PREVIOUS REVIEW:
 ***FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
  
 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
 H. N/A
 I. N/A
  
 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING:
 FOR THE LAVS:
 A. OK
 B. OK
 C. OK
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION
 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
 ***RESPONSE NOTED, BUT THE REQUIREMENT FOR SECTION
 11-4.1.3(10(A) HAS NOT BEEN ADDRESSED. THE FLOOR PLAN
 SHOWS A SINGLE DRINKING FOUNTAIN, BUT SHT A-105.1 SHOWS
 A HI/LOW. PLEASE CLARIFY. IF A SINGLE DRINKING
 FOUNTAIN, SHOW COMPLIANCE FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
  
 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT
 APPROVED FOR THE SINK AREA. SECTION 106.1.1.
 ******RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. PLEASE
 INDICATE WHERE THE RESPONSE HAS BEEN ADDRESSED.
 ***RESPONSE NOTED, BUT SHT A-107 HAS NOT BEEN
 SUBMITTED, NOR IS SHT A-107 INDICATED ON THE SHEET
 INDEX SHT A-001.
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. SHT A-105 THE FIXTURES SHALL BE ACCESSIBLE. PLEASE
 SHOW COMPLIANCE FOR THE FOLLOWING:
 ___FOR THE W/C'S:
 A. OK
 B. OK
 ___FOR THE LAV'S:
 A. OK
  
 3B. SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS FOR THE SINKS IN ROOMS 129
 & IN THE ROOM LEFT OF ROOM 115.
 ***RESPONSE NOTED, BUT SHT A-107 HAS NOT BEEN
 SUBMITTED, NOR IS SHT A-107 INDICATED ON THE SHEET
 INDEX SHT A-001.
  
 4B. GAS TO THE FUTURE GENERATOR IS AT CONTRACTORS OWN
 RISK. THERE IS NO GUARANTEE THAT THE LOCATION OF THE
 FUTURE GENERATOR WILL BE APPROVED. THERE MAY BE ZONING
 OR MECHANICAL ISSUES THAT MAY PREVENT THE GENERATOR
 FROM BEING LOCATED WHERE SHOWN.
 ***RESPONSE "COMMENT NOTED FOR FUTURE REFERENCE" WILL
 BE INDICATED ON PLANS WHEN APPROVED.
  
 5B. SHTS L1 & L2 THE LANDSCAPE FIRM LICENSE NUMBER IS
 REQUIRED IN THE TITLE BLOCK ON ALL SHEETS PER FAC
 61G1-16.004(2) & FS 481.219, 481.2055. -- STAMPED
 SIGNATURES ARE NOT APPROVED. THE SIGNATURE OF THE
 LANDSCAPE ARCHITECT IS REQUIRED.--THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT SHALL BE INDICATED
 IN THE TITLE BLOCK ON EACH SHEET.
 ***RESPONSE NOTED, SHEETS DELETED.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]