Plan Review Notes For Permit 07020441 |
Permit Number |
07020441 |
|
Review Stop |
Z |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-06 14:46:43 | ***FAILED*** | | | | DUMPSTER MUST BE A MINIMUM OF 5 FEET FROM PROPERTY | | LINES. AS SHOWN, THE DUMPSTER IS TOO CLOSE TO THE SOUTH | | PROPERTY LINE. | | | | THERE IS A FUTURE GENERATOR SHOWN ON THE PLUMBING | | PLANS. BE AWARE THAT A GENERATOR MAY NOT BE PLACED IN | | THIS LOCATION AS IT BLOCKS ACCESS TO THE PARKING AND | | DRIVE AISLE. IT WOULD APPEAR THE ONLY VIABLE ON-GROUND | | LOCATION WOULD BE IN THE PARKING ROW ALONG THE EAST | | SIDE OF THE PROPERTY. THE BUILDING REQUIRES 14 PARKING | | SPACES AND 16 ARE PROVIDED. TWO SPACES COULD BE REMOVED | | TO ACCOMMODATE THE GENERATOR. PLEASE NOTE THAT | | GENERATORS SHALL BE SCREENED TO THE SAME STANDARDS AS | | DUMPSTER ENCLOSURES. DEPENDING ON YOUR FUTURE PLANS, IT | | MAY BE PRUDENT TO CONSTRUCT A COMBINATION | | DUMPSTER/GENERATOR ENCLOSURE SO THAT A FUTURE GENERATOR | | MAY BE ACCOMMODATED PER CODE REQUIREMENTS. | | | | PLEASE SHOW CODE COMPLIANT STRIPING ON ALL PARKING | | SPACES. | | | | PLEASE CALL KELLY FREEMAN, PLANNER, AT 561-822-1435 | | WITH QUESTIONS. |
|