Plan Review Notes For Permit 07020441 |
Permit Number |
07020441 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-06-05 17:18:25 | --------------DENIED------------------ | | | | 1. M.4: FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION | | AND SMOKE CONTROL SYSTEMS SHALL BE INSTALLED IN | | ACCORDANCE WITH THE REQUIREMENTS OF THIS SECTION, AND | | THE MANUFACTURER?S INSTALLATION INSTRUCTIONS AND | | LISTING. FBC,M 607.2 | | | | 2. M.4: PLEASE SHOW MEANS OF AUXILIARY DRAIN PROTECTION | | FOR ROOFTOP PACKAGE UNITS PER FBC,M 307.2.3. | | | | 3. M.4: DUCT DETECTOR INSTALLATION DETAIL SHOWS | | DETECTOR IN RETURN DUCT. SMOKE DETECTORS SHALL BE | | INSTALLED IN SUPPLY AIR SYSTEMS WITH A DESIGN CAPACITY | | GREATER THAN 2,000 CFM IN THE SUPPLY AIR DUCT. FBC,M | | 606.2.1. | | | | 4. M.4: WALL CAP DETAIL SHOWS WALL CAP W/ BUILT-IN | | DAMPER. THIS WALL CAP WILL NOT WORK FOR INTAKE IF IT | | HAS A BACKDRAFT DAMPER. ALSO, INTAKE OPENINGS ARE TO BE | | PROTECTED IN ACCORDANCE WITH FBC,M TABLE 401.6. | | | | 5. PLEASE PROVIDE ROOF CURB TO STRUCTURE ATTACHMENT AND | | EQUIPMENT TO CURB ATTACHMENT DETAILS, SHOWING THE | | DESIGN TO MEET 140 MPH WIND LOAD REQUIREMENTS OF FBC CH | | 16. | | | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|