2007-06-28 17:27:29 | *****UNSAT**** |
| PLEASE NOTE THAT SINCE A NEW SHEET (A-106) HAS BEEN |
| ADDED, IT MUST ALSO BE REFLECTED IN THE INDEX OF |
| DRAWINGS ON A-001.TO MAINTAIN UNIFORMITY ON THE PLAN |
| SHEETS, FOLLOW THE CAPITALIZED GUIDELINES TO THE |
| COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW: |
| |
| |
| 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD |
| ITEM TO D-101 |
| |
| 2.NFPA 101- 2003 EDITION SHALL BE REFERENCED. ON |
| A-001 RECTIFY #6 UNDER CODES & STANDARDS AND ADD 2004 |
| EDITION TO THE FLORIDA FIRE PREVENTION CODE |
| |
| 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| CLASS A OR CLASS B IN EXITS AND EXIT CORRIDORS, CLASS |
| A, CLASS B, OR CLASS C IN ALL OTHER AREAS.PLEASE |
| SPECIFY.YOUR RESPONSE (ON A-106) INDICATES THAT |
| CHAPTER 38/39 SHALL COMPLY.BASED UPON AN EXISTING OR |
| A NEW OCCUPANCY,REFER TO THE APPROPIATE CHAPTER. ALSO |
| SPECIFY WHAT THE INTERIOR CLASSIFICATION ARE GOING TO |
| BE, NOT JUST QUOTING THE CODE. |
| |
| NEW COMMENT |
| |
| A.ON SHEET A-106 NOTE #1 REFERS TO NFPA 241 AS LIFE |
| SAFETY.PLEASE BE ADVISED THAT NFPA 101 IS THE LIFE |
| SAFETY CODE, WHEREAS NFPA 241 IS THE STANDARD FOR |
| SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION |
| OPERATIONS. |
| |
| |
| |
| |
| |
| |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, |
| INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH |
| ITEM WAS ADDRESSED. |
| |
| |
| |