2007-06-05 20:55:08 | ** UNSAT ** |
| |
| *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR |
| CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, |
| THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| YET ABLE TO BE MADE. |
| |
| ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM |
| PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW |
| COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS |
| WHICH WERE NOT THE SAME AS PREVIOUS SUBMITTED PLANS. |
| PLANS HAVE CHANGED DESIGNERS OF RECORD. |
| |
| |
| 1) NOTE:PLEASE SEE THIS COMMENT REMAINS THE SAME AS |
| ONLY THE CODES ON THE ELECTRICAL PLANS WERE CORRECTED. |
| THE CODES ON THE ARCHITECTURAL COVER SHEETS WHICH WERE |
| OK ON PREVIOUS PLANS ARE NOT THE SAME ON THE NEW |
| ARCHITECTURAL SHEETS? |
| ELECTRICAL CODE NOT STATED, WRONG LIFE SAFETY CODE, NOT |
| THE LATEST CORRECT FBC. |
| PLEASE ADJUST. |
| PREVIOUS REVIEW NOTE: |
| PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN SUBMITTED |
| AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECTS UNDER |
| THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE THAT |
| THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC FOR |
| ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE ARE |
| CHANGES IN THE FBC WHICH WILL AFFECT DESIGNS FOR ALL |
| TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| 2002 NFPA-72 |
| 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE NOW SEE MISSING TITLE BLOCK INFORMATION |
| FORLANDSCAPE ARCHITECT AND FIRM AS REQUIRED UNDER |
| FLORIDA ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO |
| SEE FLORIDA STATUTES AND 481.219. |
| PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND |
| PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM |
| LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| |
| 3) NOTE: PLEASE SEE THE NEW LANDSCAPE SHEETS NOW |
| CONTAIN A *RUBBERSTAMP* FOR THE REQUIRED *ORIGINAL* |
| SIGNATURE FROM THE ARCHITECT OF RECORD. PLEASE SEE FS |
| 481.221. THIS IS REQUIRED WHETHER OR NOT COMMENT IS |
| MADE BY ANY OTHER TRADE. |
| |
| 4) NOTE: PLEASE SE THE ENERGY CALCULATIONS SUBMITTED IN |
| FACT CONTAINS A *RAISED SEAL* OVER *PHOTO-COPIED* |
| SIGNATURES AND DATED SHEETS. THIS IS THE SAME ON ALL |
| LOCATIONS ON BOTH SETS OF ENERGY CALCULATIONS |
| SUBMITTED. |
| PLEASE SEE FBC 13-103.1.1.1, FLORIDA STATUTES, 471.025 |
| AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH |
| REQUIRES AN *ORIGINAL SIGNATURE* FOR ALL PLANS AND |
| DOCUMENTS SIGNED, DATED AND SEALED BY THE ENGINEER. |
| |
| 4) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS |
| FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL |
| PLANS AND LIGHTING LEGEND SHOWN. PLEASE SEE LIGHTING AS |
| SHOWN ON CALCULATIONS DOES NOT CORRELATE. MANY ARE OK, |
| HOWEVER NOT ALL. |
| PLEASE GO OVER EACH AND COORDINATE PLANS WITH |
| CALCULATIONS. |
| PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1, |
| 13-415.1.AB.1.1, 13-415.2. |
| |
| 5) NOTE: PLEASE SEE THAT PLANSNOW INDICATE SOME KIND |
| OF *FUTURE* GENERATOR ON SOME SHEETS BUT NOT ON SITE |
| PLANS, LANDSCAPE, BUILDING ELECTRICAL ETC. |
| PLEASE SEE SPECS/CUT SHEETS ARE BEING SUBMITTED FOR |
| THIS UNIT, BUT NO PROVISIONS ON ELECTRICAL PLANS ARE |
| BEING GIVEN OR INFORMATION? |
| PLEASE KNOW IF ONE IS TO BE INSTALLED BASED ON THE |
| PROPOSED LOCATION AT THE REAR OF BUILDING IT DOES NOT |
| MEET THE MINIMUM CLEARANCES FOR UNIT FROM BUILDING. |
| PLEASE SEE POSSIBLE COMMENTS FROM ZONING FOR PLACING IN |
| PARKING AREA. |
| PLEASE SEE 90.7, 110.3 |
| PLEASE KNOW THE GENERATOR WILL NO BE INCLUDED UNDER |
| THIS PERMITTED SET OF PLANS IF NOT INFORMATION IS |
| SUBMITTED OR SHOWN. THIS IS A NOTE FOR INFORMATIONAL |
| PURPOSE THAT THE UNIT AT LOCATION SHOWN DOES NOT MEET |
| CODE. |
| FBC 106.1.2 |
| |
| 6) NOTE:PLEASE COMPLETE CIRCUIT FOR ROOF TOP GFI ON |
| PLANS. PLEASE COMPLETE WHAT APPEARS TO BE A DEDICATE |
| CIRCUIT IN CONFERENCE ROOM #1. THE SYMBOL IS NOT ON |
| LEGEND AND THE CLOSET ONE MENTIONS DEDICATED CIRCUIT?? |
| PLEASE CLARIFY. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 7) NOTE: PLEASE SEE AS THE PLANS HAVE BEEN REVISED FOR |
| MECHANICAL EQUIPMENT; PLEASE SEE 424.3B FOR THE MINIMUM |
| OCP REQUIRED FOR HEAT FOR A/C UNITS. (MIN 125%) PLEASE |
| ALSO CORRELATE THE OCP SHOWN ON PANEL SCHEDULE *A* WITH |
| THE OCP SHOWN IN LOAD CALCULATIONS. |
| THIS WILL CHANGE THE BREAKER SIZE, AND CONDUCTORS. |
| 240.4,310.16. |
| |
| 8) NOTE: PLEASE INDICATE THE SIZE AND TYPE OF GROUNDING |
| ELECTRODES IN THE NEW REVISED SYSTEM AS SHOWN. LENGTH, |
| TYPE OF GROUND RODS ETC. |
| 250.50, 250.53 |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 9) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT |
| CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE. |
| PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP |
| MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS |
| 150AMPS? |
| THIS IS THE SAME AS PREVIOUS PLANS. |
| |
| 10) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL |
| *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND |
| THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED |
| FOR PANEL *D*. |
| PLEASE CORRELATE. PANEL *B* IS SHOWN AS 150AMP ON |
| SCHEDULE AND 200AMPS ON NOTES. |
| FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL |
| INFORMATION. |
| |
| 11) NOTE: PLEASE SEE PANEL *A* IS STILL SHOWN AS 200A |
| MCB ON PANEL SCHEDULE AND YET NOTES FOR PANEL *A* |
| INDICATES THIS TO BE A 225AMP PANEL? |
| |
| 12) NOTE: AS NOTED ABOVE IN NOTE 10 FOR PANEL *C*, |
| PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS AS A |
| 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC |
| 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| |
| ** PLEASE SEE THE SPECS SUBMITTED FOR THE LIGHTING |
| SWITCHES SUBMITTED ARE NOT NEEDED AS A LIGHTING CONTROL |
| *SYSTEM* IS NO LONGER INDICATED. |
| ** PLEASE SEE THE CLOCK SPEC SHEETS ARE NOT NEEDED FOR |
| SETS. THANK YOU FOR SUBMITTING TO SHOW UNIT AND |
| LISTING. |
| |
| ** PLEASE KNOW AS SOME OF THE INFORMATION ON WHETHER OR |
| NOT A GENERATOR IS GOING TO BE INSTALLED IT IS NOT |
| POSSIBLE TO REVIEW FOR THESE ITEMS. |
| |
| ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF |
| THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED. |
| |
| ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE |
| SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS |
| WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE |
| ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT |
| UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT |
| HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |