Plan Review Notes
Plan Review Notes For Permit 07020441
Permit Number 07020441
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-05 20:55:08** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 ** PLEASE ALSO SEE THERE ARE SEVERAL ITEMS FROM
 PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING AND NEW
 COMMENTS BASED ON REVISED SHEETS OR SUBMITTED DOCUMENTS
 WHICH WERE NOT THE SAME AS PREVIOUS SUBMITTED PLANS.
 PLANS HAVE CHANGED DESIGNERS OF RECORD.
  
  
 1) NOTE:PLEASE SEE THIS COMMENT REMAINS THE SAME AS
 ONLY THE CODES ON THE ELECTRICAL PLANS WERE CORRECTED.
 THE CODES ON THE ARCHITECTURAL COVER SHEETS WHICH WERE
 OK ON PREVIOUS PLANS ARE NOT THE SAME ON THE NEW
 ARCHITECTURAL SHEETS?
 ELECTRICAL CODE NOT STATED, WRONG LIFE SAFETY CODE, NOT
 THE LATEST CORRECT FBC.
 PLEASE ADJUST.
 PREVIOUS REVIEW NOTE:
 PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN SUBMITTED
 AFTER DECEMBER 8TH, 2006 WHICH PLACES PROJECTS UNDER
 THE NEW CODES ADOPTED BY THE STATE. PLEASE SEE THAT
 THIS SHALL INCLUDE 2006 REVISIONS TO THE 2004 FBC FOR
 ALL TRADES AND THE 2005 NFPA-70. PLEASE KNOW THERE ARE
 CHANGES IN THE FBC WHICH WILL AFFECT DESIGNS FOR ALL
 TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE NOW SEE MISSING TITLE BLOCK INFORMATION
 FORLANDSCAPE ARCHITECT AND FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO
 SEE FLORIDA STATUTES AND 481.219.
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE: PLEASE SEE THE NEW LANDSCAPE SHEETS NOW
 CONTAIN A *RUBBERSTAMP* FOR THE REQUIRED *ORIGINAL*
 SIGNATURE FROM THE ARCHITECT OF RECORD. PLEASE SEE FS
 481.221. THIS IS REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY ANY OTHER TRADE.
  
 4) NOTE: PLEASE SE THE ENERGY CALCULATIONS SUBMITTED IN
 FACT CONTAINS A *RAISED SEAL* OVER *PHOTO-COPIED*
 SIGNATURES AND DATED SHEETS. THIS IS THE SAME ON ALL
 LOCATIONS ON BOTH SETS OF ENERGY CALCULATIONS
 SUBMITTED.
 PLEASE SEE FBC 13-103.1.1.1, FLORIDA STATUTES, 471.025
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH
 REQUIRES AN *ORIGINAL SIGNATURE* FOR ALL PLANS AND
 DOCUMENTS SIGNED, DATED AND SEALED BY THE ENGINEER.
  
 4) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL
 PLANS AND LIGHTING LEGEND SHOWN. PLEASE SEE LIGHTING AS
 SHOWN ON CALCULATIONS DOES NOT CORRELATE. MANY ARE OK,
 HOWEVER NOT ALL.
 PLEASE GO OVER EACH AND COORDINATE PLANS WITH
 CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.AB.1.1, 13-415.2.
  
 5) NOTE: PLEASE SEE THAT PLANSNOW INDICATE SOME KIND
 OF *FUTURE* GENERATOR ON SOME SHEETS BUT NOT ON SITE
 PLANS, LANDSCAPE, BUILDING ELECTRICAL ETC.
 PLEASE SEE SPECS/CUT SHEETS ARE BEING SUBMITTED FOR
 THIS UNIT, BUT NO PROVISIONS ON ELECTRICAL PLANS ARE
 BEING GIVEN OR INFORMATION?
 PLEASE KNOW IF ONE IS TO BE INSTALLED BASED ON THE
 PROPOSED LOCATION AT THE REAR OF BUILDING IT DOES NOT
 MEET THE MINIMUM CLEARANCES FOR UNIT FROM BUILDING.
 PLEASE SEE POSSIBLE COMMENTS FROM ZONING FOR PLACING IN
 PARKING AREA.
 PLEASE SEE 90.7, 110.3
 PLEASE KNOW THE GENERATOR WILL NO BE INCLUDED UNDER
 THIS PERMITTED SET OF PLANS IF NOT INFORMATION IS
 SUBMITTED OR SHOWN. THIS IS A NOTE FOR INFORMATIONAL
 PURPOSE THAT THE UNIT AT LOCATION SHOWN DOES NOT MEET
 CODE.
 FBC 106.1.2
  
 6) NOTE:PLEASE COMPLETE CIRCUIT FOR ROOF TOP GFI ON
 PLANS. PLEASE COMPLETE WHAT APPEARS TO BE A DEDICATE
 CIRCUIT IN CONFERENCE ROOM #1. THE SYMBOL IS NOT ON
 LEGEND AND THE CLOSET ONE MENTIONS DEDICATED CIRCUIT??
 PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE SEE AS THE PLANS HAVE BEEN REVISED FOR
 MECHANICAL EQUIPMENT; PLEASE SEE 424.3B FOR THE MINIMUM
 OCP REQUIRED FOR HEAT FOR A/C UNITS. (MIN 125%) PLEASE
 ALSO CORRELATE THE OCP SHOWN ON PANEL SCHEDULE *A* WITH
 THE OCP SHOWN IN LOAD CALCULATIONS.
 THIS WILL CHANGE THE BREAKER SIZE, AND CONDUCTORS.
 240.4,310.16.
  
 8) NOTE: PLEASE INDICATE THE SIZE AND TYPE OF GROUNDING
 ELECTRODES IN THE NEW REVISED SYSTEM AS SHOWN. LENGTH,
 TYPE OF GROUND RODS ETC.
 250.50, 250.53
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT
 CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE.
 PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP
 MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS
 150AMPS?
 THIS IS THE SAME AS PREVIOUS PLANS.
  
 10) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL
 *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND
 THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED
 FOR PANEL *D*.
 PLEASE CORRELATE. PANEL *B* IS SHOWN AS 150AMP ON
 SCHEDULE AND 200AMPS ON NOTES.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 11) NOTE: PLEASE SEE PANEL *A* IS STILL SHOWN AS 200A
 MCB ON PANEL SCHEDULE AND YET NOTES FOR PANEL *A*
 INDICATES THIS TO BE A 225AMP PANEL?
  
 12) NOTE: AS NOTED ABOVE IN NOTE 10 FOR PANEL *C*,
 PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS AS A
 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC
 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 ** PLEASE SEE THE SPECS SUBMITTED FOR THE LIGHTING
 SWITCHES SUBMITTED ARE NOT NEEDED AS A LIGHTING CONTROL
 *SYSTEM* IS NO LONGER INDICATED.
 ** PLEASE SEE THE CLOCK SPEC SHEETS ARE NOT NEEDED FOR
 SETS. THANK YOU FOR SUBMITTING TO SHOW UNIT AND
 LISTING.
  
 ** PLEASE KNOW AS SOME OF THE INFORMATION ON WHETHER OR
 NOT A GENERATOR IS GOING TO BE INSTALLED IT IS NOT
 POSSIBLE TO REVIEW FOR THESE ITEMS.
  
 ** PLEASE SEE ONE SET OF PLANS IS REDLINED FOR MANY OF
 THESE ITEMS WHICH MAY HELP TO LOCATE ITEMS AS NOTED.
  
 ** PLEASE KNOW AS STATED ON PREVIOUS REVIEW: PLEASE BE
 SURE TO CALL IF THERE ARE ANY QUESTIONS OR COMMENTS
 WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF THERE ARE
 ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, NOT
 UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE AND THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717