Plan Review Notes
Plan Review Notes For Permit 07020441
Permit Number 07020441
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-13 13:55:54DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3 SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER
 SECTION 11-4.16.2, THE DRINKING FOUNTAIN PER SECTION
 11-4.15.5, AND THE KITCHEN SINK PER SECTION 11-4.24.5,
 (FORWARD APPROACH REQUIRED).
  
 2. SHT A-8 PLUMBING SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE
 REQUIREMENTS. TOILET ROOMS #2 SHOW A W/C & A LAV IN
 EACH ROOM ON THE FLOOR PLAN, BUT ON THE RISER DIAGRAM
 AS DRAWN IT INDICATES BOTH W/C'S IN ONE ROOM AND BOTH
 LAVS IN ANOTHER. ALSO THE W/C'S ARE SHOWN CONNECTING TO
 THE BRANCH LINE & TO THE BUILDING DRAIN LINE. W/C'S
 SHALL BE CONNECTED TO THE BRANCH LINE ONLY.--ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT. SECTION 909.1. ALL OTHER FIXTURES BESIDES THE
 FIXTURES IN TOILET ROOMS #2 SHALL CONNECT DOWNSTREAM OF
 THE FIXTURES ON TOILET ROOMS #2.--TOILET ROOMS #1
 ARE SHOWN ON THE LEFT OF TOILET ROOMS #2 ON THE FLOOR
 PLAN, BUT ARE SHOWN ON THE RIGHT SIDE OF TOILET ROOMS
 #2 ON THE RISER DIGARAM.--THE DRINKING FOUNTAIN IS
 NOT SHOWN ON THE RISER DIAGRAM. CORRELATE FLOOR PLAN
 AND RISER. SECTION 106.1.1.--THE LAVS AND W/C'S IN
 TOILET ROOMS #1 ARE NOT VENTED AS SHOWN. SECTION
 901.2.1.--TRAPS ARE NOT ALLOWED FOR THE W/C'S AS
 THEY HAVE INTEGRAL TRAPS BUILT IN THEM. SECTION 1002.1.
 (SEE ONE SET OF PLANS SHT A-8 FOR AN EXAMPLE OF A RISER
 DIAGRAM THAT REFLECTS THE FLOOR PLAN AND MEETS CODE
 REQUIREMENTS).
  
 3. SUBMIT A WATER RISER DIAGRAM THAT REFLECT THE FLOOR
 PLAN. SHOW ALL PIPE SIZES, VALVES ECT. SECTION
 106.3.5.1.3(3)(10)(13).
  
 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED
 GAS PERMIT:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (SHOW THE LENGTH FROM THE METER TO THE
 FIRST RISER),
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 H. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 I. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING:
 FOR THE LAVS:
 A. 11-4.19.2 CLEARANCE (29")
 B. 11-4.19.4 EXPOSED PIPES & SURFACES
 C. 11-4.91.5 FAUCETS
  
 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING
 COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS
 WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION
 106.1.1.
  
 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING
 COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS.
 SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT
 APPROVED FOR THE SINK AREA. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]