2007-03-13 13:55:54 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A-3 SHOW THE CLEAR FLOOR SPACE FOR THE W/C'S PER |
| SECTION 11-4.16.2, THE DRINKING FOUNTAIN PER SECTION |
| 11-4.15.5, AND THE KITCHEN SINK PER SECTION 11-4.24.5, |
| (FORWARD APPROACH REQUIRED). |
| |
| 2. SHT A-8 PLUMBING SANITARY RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| REQUIREMENTS. TOILET ROOMS #2 SHOW A W/C & A LAV IN |
| EACH ROOM ON THE FLOOR PLAN, BUT ON THE RISER DIAGRAM |
| AS DRAWN IT INDICATES BOTH W/C'S IN ONE ROOM AND BOTH |
| LAVS IN ANOTHER. ALSO THE W/C'S ARE SHOWN CONNECTING TO |
| THE BRANCH LINE & TO THE BUILDING DRAIN LINE. W/C'S |
| SHALL BE CONNECTED TO THE BRANCH LINE ONLY.--ONLY |
| THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY |
| ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE |
| WET VENT. SECTION 909.1. ALL OTHER FIXTURES BESIDES THE |
| FIXTURES IN TOILET ROOMS #2 SHALL CONNECT DOWNSTREAM OF |
| THE FIXTURES ON TOILET ROOMS #2.--TOILET ROOMS #1 |
| ARE SHOWN ON THE LEFT OF TOILET ROOMS #2 ON THE FLOOR |
| PLAN, BUT ARE SHOWN ON THE RIGHT SIDE OF TOILET ROOMS |
| #2 ON THE RISER DIGARAM.--THE DRINKING FOUNTAIN IS |
| NOT SHOWN ON THE RISER DIAGRAM. CORRELATE FLOOR PLAN |
| AND RISER. SECTION 106.1.1.--THE LAVS AND W/C'S IN |
| TOILET ROOMS #1 ARE NOT VENTED AS SHOWN. SECTION |
| 901.2.1.--TRAPS ARE NOT ALLOWED FOR THE W/C'S AS |
| THEY HAVE INTEGRAL TRAPS BUILT IN THEM. SECTION 1002.1. |
| (SEE ONE SET OF PLANS SHT A-8 FOR AN EXAMPLE OF A RISER |
| DIAGRAM THAT REFLECTS THE FLOOR PLAN AND MEETS CODE |
| REQUIREMENTS). |
| |
| 3. SUBMIT A WATER RISER DIAGRAM THAT REFLECT THE FLOOR |
| PLAN. SHOW ALL PIPE SIZES, VALVES ECT. SECTION |
| 106.3.5.1.3(3)(10)(13). |
| |
| 4. SUBMIT THE FOLLOWING INFORMATION FOR THE REQUIRED |
| GAS PERMIT: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. (SHOW THE LENGTH FROM THE METER TO THE |
| FIRST RISER), |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| H. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| I. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| 5. SHT A-8 SHOW COMPLIANCE FOR THE FOLLOWING: |
| FOR THE LAVS: |
| A. 11-4.19.2 CLEARANCE (29") |
| B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| C. 11-4.91.5 FAUCETS |
| |
| 6. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| COMPLIANCE WITH SECTION 11-4.15AND ALL SUBSECTIONS, AS |
| WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| WHO HAVE DIFFICULTY BENDING OR STOOPING. SECTION |
| 106.1.1. |
| |
| 7. SUBMIT A DETAIL FOR THE KITCHEN SINK SHOWING |
| COMPLIANCE WITH SECTION 11-4.24 AND ALL SUBSECTIONS. |
| SUBMIT AN ELEVATION VIEW. CABINET DOORS ARE NOT |
| APPROVED FOR THE SINK AREA. SECTION 106.1.1. |
| |
| REVIEW BY KEN STEVENS |