Plan Review Notes
Plan Review Notes For Permit 07020441
Permit Number 07020441
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-17 16:53:40------------------DENIED-------------------
  
 1. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS. FBC
 106.3.5.1.4
  
 2. PLEASE PROVIDE SUBMITTAL DATA FOR THE FIREPLACE
 INCLUDING MANUFACTURER'S INSTRUCTIONS RELATED TO
 VENTING REQUIREMENTS.
  
 3. DUCT SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR
 THE ENTIRE AIRFLOW OF THE SYSTEM PER FBC,M 606.3. TO
 ACCOMPLISH THIS, THE DETECTOR NEEDS TO BE LOCATED IN
 THE SUPPLY TRUNK BEFORE FIRST TAP OR BRANCH DUCT.
 CONSULT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS
 FOR MINIMUM REQUIRED DISTANCE FROM BLOWER. AN
 AUDIBLE/VISIBLE NOTIFICATION (HORN/STROBE) IN AN
 APPROVED LOCATION IS REQUIRED UPON ACTIVATION OF THE
 SMOKE DETECTOR PER FBC,M 606.4.1(2)
  
 4. SOME TRANSFER DUCTS (JUMPERS) ARE NOT SIZED TO MEET
 THE BALANCED RETURN AIR EXCEPTIONS AS LISTED IN FBC,M
 601.4. IF THESE EXCEPTIONS ARE NOT MET, A FIELD TEST
 WILL BE REQUIRED AT FINAL INSPECTION TO SHOW THAT THE
 REQUIREMENT FOR A MAXIMUM PRESSURE DIFFERENTIAL OF
 0.01" WC HAS BEEN ACHIEVED.
  
 REVIEWED BY:
 RONALD J REGUEIRO
 561.805.6719
 [email protected]