2007-03-17 16:53:40 | ------------------DENIED------------------- | | | | 1. PLEASE PROVIDE AN EQUIPMENT SCHEDULE ON PLANS. FBC | | 106.3.5.1.4 | | | | 2. PLEASE PROVIDE SUBMITTAL DATA FOR THE FIREPLACE | | INCLUDING MANUFACTURER'S INSTRUCTIONS RELATED TO | | VENTING REQUIREMENTS. | | | | 3. DUCT SMOKE DETECTORS SHALL BE INSTALLED TO MONITOR | | THE ENTIRE AIRFLOW OF THE SYSTEM PER FBC,M 606.3. TO | | ACCOMPLISH THIS, THE DETECTOR NEEDS TO BE LOCATED IN | | THE SUPPLY TRUNK BEFORE FIRST TAP OR BRANCH DUCT. | | CONSULT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS | | FOR MINIMUM REQUIRED DISTANCE FROM BLOWER. AN | | AUDIBLE/VISIBLE NOTIFICATION (HORN/STROBE) IN AN | | APPROVED LOCATION IS REQUIRED UPON ACTIVATION OF THE | | SMOKE DETECTOR PER FBC,M 606.4.1(2) | | | | 4. SOME TRANSFER DUCTS (JUMPERS) ARE NOT SIZED TO MEET | | THE BALANCED RETURN AIR EXCEPTIONS AS LISTED IN FBC,M | | 601.4. IF THESE EXCEPTIONS ARE NOT MET, A FIELD TEST | | WILL BE REQUIRED AT FINAL INSPECTION TO SHOW THAT THE | | REQUIREMENT FOR A MAXIMUM PRESSURE DIFFERENTIAL OF | | 0.01" WC HAS BEEN ACHIEVED. | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|