2007-03-29 14:08:42*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.NFPA 101- 2003 EDITION SHALL BE REFERENCED.
  
 3.INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE
 CLASS A OR CLASS B IN EXITS AND EXIT CORRIDORS, CLASS
 A, CLASS B, OR CLASS C IN ALL OTHER AREAS.PLEASE
 SPECIFY.
  
 4.SHOW LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.IF THE BUILDING IS EQUIPPED WITH A FIRE ALARM AND
 (OR) FIRE SPRINKLER SYSTEM, WILL THE SCOPE OF WORK
 CAUSE THE SYSTEM(S) TO BE MODIFIED?IF SO, SEPARATE
 PLANS AND PERMIT WILL BE REQUIRED FOR THE REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED.
  
  
  