Plan Review Notes
Plan Review Notes For Permit 07020441
Permit Number 07020441
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-04 17:09:14** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWINGON ELECTRICAL SHEETS FOR
 THIS REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS.(ALREADY ON MAIN
 ARCHITECTURAL SHEETS)
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING TITLE BLOCK INFORMATION FOR
 ARCHITECT AND FIRM AS REQUIRED UNDER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004. PLEASE ALSO SEE
 FLORIDA STATUTES AND 481.219.
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNER AND MISSING FIRM
 LICENSE NUMBER ALSO KNOWN AS THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
  
 3) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING WHICH CORRELATES WITH THE ELECTRICAL
 PLANS AND LIGHTING SHOWN. PLEASE SEE LIGHTING AS SHOWN
 ON CALCULATIONS DOES NOT CORRELATE.
 PLEASE ALSO BE SURE THESE ARE SIGNED, DATED AND SEALED
 BY THE DESIGNER OF RECORD AND THE PERSON RESPONSIBLE
 FOR ENERGY CALCULATIONS.
 PLEASE SEE THAT AN AUTOMATED METHOD OF LIGHTING
 CONTROLS IS BEING NOTED ON SYMBOL LEGEND HOWEVER THE
 ENERGY CALCULATIONS DO NOT CORRELATE WITH THIS AS THEY
 SHOW *MANUAL ON/OFF* FOR THIS?
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.AB.1.1, 13-415.2,AND 13-415.2.ABC.1.2 (3)
 FOR TRACK LIGHTING (WHERE APPLICABLE)
  
 4) NOTE: PLEASE SEE THAT PLANS DO INDICATE SOME
 CONTROLS FOR LIGHTING HOWEVER PLEASE SUBMIT MORE
 INFORMATION FOR SYSTEM BEING PROPOSED.
 FBC 106.1.2 ADMIN SECTION
 110.3, 90.7 NEC.
  
 5) NOTE: PLEASE SEE THE ACCESS TO THE ELECTRICAL ROOM
 WILL NOT BE PERMITTED THROUGH A STORAGE ROOM. 240.24.
 PLEASE KNOW THAT ALL ACCESS TO OVER CURRENT PROTECTION
 DEVICES SHALL BE ACCESSIBLE ON A CONTINUING BASIS.
 PLEASE KNOW THIS IS REQUIRED BY THIS OFFICE AND THE
 OFFICE OF THE FIRE MARSHAL.
 PLEASE SEE THE LOCATION OF THE PANEL *D* IS BEING NOTED
 AND SHOWN IN A STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL(S) NEED TO MEET 110.26.
 PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
  
 6) NOTE:PLEASE SEE PLANS ON ARCHITECTURAL SHEETS
 NOTES SERVICE AS EXISTING HOWEVER THE ELECTRICAL PLANS
 AND RISER SEEM TO NOTE AND INDICATE ALL OF THIS
 EQUIPMENT AS NEW. PLEASE CLARIFY AND ADJUST NOTE ON
 ARCHITECTURAL PLANS IF ALL NEW AS SHOWN.
 FBC 106.1.2, 106.3.5.1.2
  
 7) NOTE: PLEASE KNOW THAT THE PLANS NEED TO CORRELATE
 WITH ALL CIRCUIT DESIGNATIONS ON PLANS FOR ROOMS AND
 AREAS. PLEASE SEE TEXT WHICH IS TAKEN FROM COMMENTARY
 IN THE CODE WHICH STATES THE USE OF *GEN LT* ETC IS NOT
 ACCEPTABLE.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE
 M-SHEETS DO NOT SEEM TO INDICATE ANY MECHANICAL
 EQUIPMENT. PLEASE KNOW THAT REVIEW OF EQUIPMENT FOR
 ELECTRICAL COMPLIANCE CAN NOT BE DONE AT THIS TIME.
 PLEASE COMPLETE.
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PLEASE SEE PANEL SCHEDULE *A* IS NOT COMPLETE
 FOR CONDUCTOR SIZES REQUIRED FOR AC EQUIPMENT. PLEASE
 ALSO SEE MISSING LOAD FOR THE RTU.
 PLEASE COMPLETE FOR REVIEW OF CODE COMPLIANCE. 310.16,
 240.4, 220, 408.4
  
 10) NOTE: PLEASE SEE 700.12E FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. PLEASE SEE MOST ARE
 CIRCUITED CORRECTLY AND ONLY ONE OR SO IS CIRCUITED TO
 OTHER THAN THE LOCAL LIGHTING BRANCH CIRCUIT.
  
 11) NOTE: PLEASE CLARIFY MEZZANINE LEVEL FOR LIGHTING
 AND CONTROL.
 PLEASE KNOW LIGHTING CONTROL WILL ALSO BE REQUIRED AT
 THE MEZZ LEVEL AND RECEPTACLE FOR SERVICE PER 210.63,
 210.70.
  
 12) NOTE: PLEASE SEE PANEL *C* ON RISER WHICH DOES NOT
 CORRELATE WITH THE NUMERICAL ELECTRICAL RISER NOTE.
 PLEASE SEE NOTE MENTIONS 100AMP PANEL WITH A 200AMP
 MAIN BREAKER YET PANEL SCHEDULE SHOWS THIS PANEL AS
 150AMPS?
  
 13) NOTE: PLEASE SEE PANEL *B* AND NOTE ABOVE FOR PANEL
 *C*. PLEASE CORRELATE WITH ELECTRICAL NOTES ALSO AND
 THE RISER WHICH SHOWS NOTE #10. NOTE #10 IS ALSO USED
 FOR PANEL *D*.
 PLEASE CORRELATE.
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 14) NOTE: PLEASE SEE NOTE FOR GROUNDING ELECTRODE
 SYSTEM MENTIONS NEW *BLDG STEEL* YET THIS BEING AN
 EXISTING BUILDING IT IS UNCLEAR WHERE THE NEW BUILDING
 STEEL IS BEING SHOWN. REVIEW OF ARCHITECTURAL AND
 STRUCTURAL PLANS DOES NOT REVEAL THIS.
 PLEASE KNOW AS AN EXISTING BUILDING THE FOOTER STEEL IS
 NOT A REQUIRED ATTACHMENT UNLESS NEW.OPENING OF THE
 OLDER EXISTING FOOTER TO MAKE AN ATTACHMENT COULD
 CREATE ISSUES FOR THE STRUCTURAL INTEGRITY OF THE
 EXISTING FOOTER DEPENDING ON THE AGE ETC.
 250.50
  
 15) NOTE: PLEASE CORRELATE THE CIRCUITING FOR CLOCK
 FEED AS THE LOAD AND AMPERAGE ON THE PANEL SCHEDULE,
 PLANSAND LOAD CALCULATIONS LEND THIS TO BE A 20AMP
 AND SINGLE POLE CIRCUIT, HOWEVER THE PANEL SCHEDULE
 SHOWS THIS FEED AS A 2-POLE 30AMP CIRCUIT WITH #10
 AWG?
 PLEASE CORRELATE.
 FBC 106.3.5.1.2
  
 16) NOTE: PLEASE SEE PANEL *D* NOTE WHICH MENTIONS THIS
 AS A 200AMP MCB PANEL YET, PANEL IS SHOWN AS MLO. FBC
 106.3.5.1.2, 106.1.2 FOR COORDINATION.
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT SUBMITTED AT
 THIS TIME FOR REVIEW THER MAY BE COMMENTS ON ANY
 FOLLOWING REVIEWS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]