2007-03-15 16:21:46 | BUILDING PLAN REVIEW |
| PERMIT: 07020441 |
| ADD: 6600S DIXIE HWY |
| CONT: S. E. C. CONSTRUCTION & DEV |
| TEL: (561)797-6007 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW |
| ACTION: DENIED |
| |
| 1) --- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH |
| NOTICE IS NULL & VOID. NOTE: 713.13(6) THE POSTING OF |
| THE NOTICE OF |
| COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| INSPECTION. |
| |
| 3) COVER SHEET A-1 DESIGN DATA INDICATES THE DESIGN TO |
| ASCE 7-98, THE CURRENT STANDARD UNDER THE 2006 FBC IS |
| ASCE 7-02. |
| |
| 4) PLANS ALSO INDICATE THERE ARE NO OPENINGS IN END |
| ZONES, 10% OF 55'-2"OR 5'-2" OR 40% OF BUILDING MEAN |
| ROOF HEIGTH13'-0"= 5'-21/2", PLEASE CORRECT THE WINDOWS |
| PRESSURES IN THE END ZONES. TABLE 1609.6B. |
| |
| 5) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 6) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 7) FRONT DOOR TO BE BUILT AS A ONE TIME APPROVAL , THE |
| DESIGNER OF RECORD WILL NEED TO SUPERVISE |
| THE ASSEMBLY OF THE DOOR AND THE INSTALATION OF DOOR |
| AND FRAME, AND SIGN AND SEAL AFFADAVIT TO THE EFFECT. |
| THIS WILL BE A PROVISO REQUIRED BEFORE A CERTIFICATE OF |
| COMPLETION CAN BE ISSUED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |