Plan Review Notes
Plan Review Notes For Permit 07020425
Permit Number 07020425
Review Stop B
Sequence Number 1
Notes
Date Text
2007-02-20 10:28:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2001
  
 1.)SELECT THE APPROVED ASSEMBLY YOU ARE USING FOR THE
 METAL ROOF.NOTE THAT ONLY ONE IS COMPLIANT FOR THE
 DESIGN PRESSURE OF ZONE 3, -89 PSF (SHEET S3).
  
 2.)THE ASSEMBLY YOU HAVE SELECTED FOR THE FLAT DECK
 REFERS TO GENERAL LIMITATION #9 WHICH DOES NOT ALLOW
 ENHANCED FASTENING.THE ASSEMBLY MAXIMUM DESIGN
 PRESSURE OF -45 IS NOT COMPLIANT FOR ZONES 2 (-59.2)
 AND 3 (-89).
  