Plan Review Notes For Permit 07020389 |
Permit Number |
07020389 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-02-20 14:40:09 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) PLEASE PROVIDE RETURN AIR TO BEDROOMS, BALANCED | | RETURN AIR MAY BE ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE | | RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS | | SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR | | HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO | | ACHIEVE PROPER RETURN AIR BALANCE. | | (B)TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF | | GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING | | THROUGH-THE-WALL TRANSFER GRILLES AND USING AN | | UNRESTRICTED 1-INCH UNDERCUTTING OF DOORS TO ACHIEVE | | PROPER RETURN AIR BALANCE | | (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET | | THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR | | EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY | | ROOMS, EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE | | SHALL BE INCLUDED. PER 2004 FBC/R M1602.4 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|