2007-03-13 17:04:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)ON SHEET 8 OF THE ASSA PRODUCT APPROVAL, YOU HAVE
 CIRCLED 47.8, MAX OF 12' SPAN.SEE OPENING 3, 66 PSF
 EXCEEDS THE MAXIMUM PANEL SPAN.THE INFORMATION
 CIRCLED ON THE PRODUCT APPROVAL SHOULD CORRELATE WITH
 THE JOB.
  
 2.)4" SPACING IS REQUIRED FOR SPANS OVER 8'6,
 61.9-75.3 PSF.YOU HAVE SPECIFIED 8" ON THE
 INSTALLATION SCHEDULE.
  
 3.)YOU HAVE CIRCLED 6' SPAN ON THE CHART FOR THE
 PANELS, BUT THE 85" OPENING DOES NOT SPECIFY IF YOU ARE
 INSTALLING VERTICALLY OR HORIZONTALLY SO SHOULD USE THE
 WORST CONDITION.THE ANCHORING IS THE SAME, BUT THE
 INFORMATION CIRCLED ON THE PRODUCT APPROVAL SHOULD
 CORRELATE WITH THE INSTALLATION SCHEDULE. \
  
 4.)PLEASE CONTACT ME IF YOU NEED ASSISTANCE IN
 DETERMINING HOW TO SUBMIT CODE COMPLIANT PAPERWORK.