2008-01-10 10:50:46 | 2004 FBC W/2006 REVISIONS |
| LEVEL 2 ALTERATION AND ADDITION |
| |
| REVISION TO ENCLOSE CARPORT INTO A GARAGE IS DENIED BY |
| BUILDING |
| |
| 1) SPECIFY THE VALUE OF THE ADDITIONAL WORK (CURRENTLY |
| $21,013.00) AND PAY ADDITIONAL PERMIT FEES. SEE FBC |
| 108.1* AND 108.2* CITY AMENDMENTS. |
| |
| 2) WHEN MAKING REVISIONS TO APPROVED PLANS, THE NEW |
| PLANS ARE REQUIRED TO CONTAIN THE INFORMATION ON THE |
| OLD DRAWINGS THAT IS NOT BEING CHANGED, AS WELL AS, THE |
| NEW INFORMATION. THE REVISED/NEW INFORMATION SHOULD BE |
| CLOUDED AND LABELED WITH THE REVISION NUMBER. SEE FBC |
| 106.1.3* AND 106.1.1* CITY AMENDMENTS. NOTE: THESE |
| PLANS NEED TO SHOW THE SCOPE OF WORK FOR THE ENTIRE |
| PROJECT IN ADDITION TO THE REVISION TO ENCLOSE THE |
| GARAGE. SOME OF THE INFORMATION FROM THE APPROVED PLANS |
| WAS NOT SHOWN ON THE REVISED SHEET A-1. |
| |
| 3) COMPLIED. |
| |
| 4) THE WEST ELEVATION WAS ADDED TO PLANS. HOWEVER, THE |
| EAST ELEVATION WAS ELIMINATED. PLEASE SHOW BOTH |
| ELEVATIONS ON THE DRAWINGS. FBC 106.1.1* CITY |
| AMENDMENTS. |
| |
| 5) COMPLIED. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| DOOR, THE SIDE SWING GARAGE DOOR, THE ROOF COVERING. |
| SEE FAC RULE 9B-72. THE PRODUCT APPROVALS THAT WERE |
| SUBMITTED ARE FOR GAF RIDGE CAP SHINGLES AND THEY WERE |
| NOT APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| |
| 9)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 10) COMPLIED. |
| |
| 11) SHOW COMPLIANCE WITHR302.1 EXTERIOR WALLS. |
| EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| AN ADJACENT PROJECTION OR WALL. PROJECTIONS EXTENDING |
| INTO THE 6-FOOT (1829 MM) SEPARATION DISTANCE SHALL |
| HAVE NOT LESS THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION |
| ON THE UNDERSIDE. |
| R302.2 OPENINGS. |
| OPENINGS SHALL NOT BE PERMITTED IN THE EXTERIOR WALL OF |
| A DWELLING OR ACCESSORY BUILDING THAT IS SEPARATED FROM |
| AN ADJACENT BUILDING BY A DISTANCE OF LESS THAN 6 FEET |
| (1828 MM). THIS DISTANCE SHALL BE MEASURED |
| PERPENDICULAR TO THE LINE USED TO DETERMINE THE |
| SEPARATION DISTANCE. |
| THE NEW GARAGE WALLS APPEAR TO BE LESS THAN 6 FEET FROM |
| THE PROPERTY LINE. PROVIDE A SURVEY/SITE PLAN THAT |
| INDICATES THAT THE DISTANCE TO STRUCTURES ON THE |
| ADJACENT PROPERTY WILL COMPLY WITH THE REQUIRED |
| DISTANCES OR COMPLY WITH THE CODE SECTIONS LISTED |
| ABOVE. |
| |