2007-11-26 10:40:11 | 2004 FBC W/2006 REVISIONS |
| LEVEL 2 ALTERATION AND ADDITION |
| |
| REVISION TO ENCLOSE CARPORT INTO A GARAGE IS DENIED BY |
| BUILDING |
| |
| 1) SPECIFY THE VALUE OF THE ADDITIONAL WORK (CURRENTLY |
| $21,013.00) AND PAY ADDITIONAL PERMIT FEES. SEE FBC |
| 108.1* AND 108.2* CITY AMENDMENTS. |
| |
| 2) WHEN MAKING REVISIONS TO APPROVED PLANS, THE NEW |
| PLANS ARE REQUIRED TO CONTAIN THE INFORMATION ON THE |
| OLD DRAWINGS THAT IS NOT BEING CHANGED, AS WELL AS, THE |
| NEW INFORMATION. THE REVISED/NEW INFORMATION SHOULD BE |
| CLOUDED AND LABELED WITH THE REVISION NUMBER. SEE FBC |
| 106.1.3* AND 106.1.1* CITY AMENDMENTS. |
| |
| 3) THE DETAILS ON SHEET D-1 DO NOT CORRESPOND WITH THE |
| FRONT ELEVATION SHOWN ON A-1. THE ELEVATION SHOWS A |
| GABLE AT THE RIGHT SIDE. PLEASE CLARIFY. FBC 106.1.1* |
| CITY AMENDMENTS |
| |
| 4) THE RIGHT SIDE ELEVATION IS NOT LABELED ON SHEET |
| A-1. FBC 106.1.1* CITY AMENDMENTS |
| |
| 5) SPECIFY THE SIZE AND SPACING OF THE ROOF RAFTERS. |
| FBC 106.1.1* CITY AMENDMENTS |
| |
| 6) SPECIFY THE SPACING OF THE 2 X 6 WALL FRAMING. FBC |
| 106.1.1* CITY AMENDMENTS |
| |
| 7) SPECIFY THE WALL COVERING FOR THE GABLE END ON THE |
| RIGHT ELEVATION. FBC 106.1.1* CITY AMENDMENTS |
| |
| 8) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| DOOR, THE SIDE SWING GARAGE DOOR, THE ROOF COVERING. |
| SEE FAC RULE 9B-72. |
| |
| 9)106.3* PRODUCT APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE REVIEWED AND |
| APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| 10) THE ROOF SHEATHING NAILING INFORMATION ON SHEET D-1 |
| IS INCORRECT. PLEASE REVISE. ROOF SHEATHING IS REQUIRED |
| TO BE IN ACCORDANCE WITH SECTION R803.2.3.1 OF 2006 |
| REVISIONS TO 2004 FBC RESIDENTIAL CODE. WOOD STRUCTURAL |
| PANEL SHEATHING SHALL BE FASTENED TO ROOF FRAMING WITH |
| 8D RING-SHANK NAILS AT 6 INCHES ON CENTER AT EDGES AND |
| 6 INCHES ON CENTER AT INTERMEDIATE FRAMING. SPACING OF |
| RING-SHANK FASTENERS SHALL BE 4 INCHES ON CENTER IN |
| NAILING ZONE 3 FOR 130 MPH OR GREATER DESIGN WIND |
| SPEEDS IN ACCORDANCE WITH FIGURE R803.2.3.1. |
| |
| - ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |