Plan Review Notes
Plan Review Notes For Permit 07020358
Permit Number 07020358
Review Stop B
Sequence Number 3
Notes
Date Text
2007-07-06 10:44:39DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE SYSTEM THAT WAS SELECTED FOR THE FIRESTONE
 MODIFIED ROOF SYSTEM ON PAGE 31 OF NOA 05-0830.10, DOES
 NOT ALLOW ENHANCED FASTENING TO INCREASE THE DESIGN
 PRESSURE. THEREFORE, THE CALCULATIONS FROM THE ENGINEER
 FOR ENHANCED FASTENING ARE NOT ALLOWED. SEE LIMITATION
 #9 ON PAGE 34 OF THE NOA. ONE SET OF THE ENGINEER'S
 CALCULATIONS HAVE BEEN RETAINED.
  
 3) THE ENERGY CALCULATION FORM THAT WAS SUBMITTTED IS
 OUTDATED. SUBMIT THE CURRENT ONE, WHICH IS FORM
 600C-04.
  
 4) THE OWNER/ AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714