2007-04-26 10:17:44 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT TWO CLEAR AND LEGIBLE COPIES OF ALL PRODUCT |
| APPROVALS. NOTE: THESE WILL BE COPIED INTO FILES FOR |
| RECORD RETENTION. THEREFORE, THEY MUST BE CLEAR AND |
| READABLE. |
| |
| 4)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. SEE THE FL. COVERSHEET FOR THE FIRESTONE ROOFING |
| MATERIAL ATTACHED TO THIS REVIEW. |
| |
| 5)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. THE LETTER FROM THE |
| DESIGNER OF RECORD DOES NOT INCLUDE ALL OF THE ITEMS |
| REQUIRED TO HAVE PRODUCT APPROVALS SUBMITTED BY RULE |
| 9B-72. |
| |
| 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK, THE |
| OUTSWING EXTERIOR GARAGE DOOR, THE 8' X 7' OVERHEAD |
| GARAGE DOOR, THE SIMPSON AND USP CONNECTORS AND THE |
| SINGLE HUNG WINDOWS. |
| |
| 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT |
| SGD-70, SLIDING GLASS DOOR, HAS PAGES OF THE NOA THAT |
| ARE ILLEGIBLE. THE ENTIRE REPORT MUST BE LEGIBLE. |
| |
| 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED |
| IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL |
| BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL |
| BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY. |
| CIRCLE THE APPROPRIATE ITEMS ON THE NOA. THE REQUIRED |
| UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 AND -89.0 |
| FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO LOW |
| FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS PER |
| GENERAL LIMITATION #7. SEE PAGE 34 OF THE NOA. |
| |
| 9) NO ENERGY CALCULATIONS WERE SUBMITTED. PLEASE SUBMIT |
| THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS REQUIRED |
| TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER 13. |
| |
| 10) AN EMERGENCY ESCAPE AND RESCUE OPENING TO THE |
| EXTERIOR REQUIRED BY FBC R310 MUST BE PROVIDED AT THE |
| EXISTING BEDROOM ADJACENT TO THE ADDITION WHICH HAS THE |
| REAR WINDOWSTHAT ARE BEING ENCLOSED. |
| |