Plan Review Notes
Plan Review Notes For Permit 07020358
Permit Number 07020358
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-26 10:17:44DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO CLEAR AND LEGIBLE COPIES OF ALL PRODUCT
 APPROVALS. NOTE: THESE WILL BE COPIED INTO FILES FOR
 RECORD RETENTION. THEREFORE, THEY MUST BE CLEAR AND
 READABLE.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. SEE THE FL. COVERSHEET FOR THE FIRESTONE ROOFING
 MATERIAL ATTACHED TO THIS REVIEW.
  
 5)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. THE LETTER FROM THE
 DESIGNER OF RECORD DOES NOT INCLUDE ALL OF THE ITEMS
 REQUIRED TO HAVE PRODUCT APPROVALS SUBMITTED BY RULE
 9B-72.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK, THE
 OUTSWING EXTERIOR GARAGE DOOR, THE 8' X 7' OVERHEAD
 GARAGE DOOR, THE SIMPSON AND USP CONNECTORS AND THE
 SINGLE HUNG WINDOWS.
  
 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT
 SGD-70, SLIDING GLASS DOOR, HAS PAGES OF THE NOA THAT
 ARE ILLEGIBLE. THE ENTIRE REPORT MUST BE LEGIBLE.
  
 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL
 BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL
 BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY.
 CIRCLE THE APPROPRIATE ITEMS ON THE NOA. THE REQUIRED
 UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 AND -89.0
 FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO LOW
 FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS PER
 GENERAL LIMITATION #7. SEE PAGE 34 OF THE NOA.
  
 9) NO ENERGY CALCULATIONS WERE SUBMITTED. PLEASE SUBMIT
 THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS REQUIRED
 TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER 13.
  
 10) AN EMERGENCY ESCAPE AND RESCUE OPENING TO THE
 EXTERIOR REQUIRED BY FBC R310 MUST BE PROVIDED AT THE
 EXISTING BEDROOM ADJACENT TO THE ADDITION WHICH HAS THE
 REAR WINDOWSTHAT ARE BEING ENCLOSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  