Plan Review Notes
Plan Review Notes For Permit 07020358
Permit Number 07020358
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-09 11:16:14DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: SHEET E-1 ISOMETRIC SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN ON SHEET A-1. SHEET A-1
 INDICATES A NEW KITCHEN WITH A DOUBLE BOWL KITCHEN SINK
 WITH DISHWASHER BUT ON SHEET E-1 ISOMETRIC SANITARY
 RISER DIAGRAM THE WASTE PIPING TO THE NEW KITCHEN IS
 NOT INDICATED. PLEASE REFERENCE THE ATTACHED CORRECTED
 ISOMETRIC SANITARY RISER DIAGRAM TO THE PLUMBING
 COMMENTS THAT REFLECTS THE FLOOR PLAN AND IS CODE
 COMPLIANT FOR THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  