Plan Review Notes
Plan Review Notes For Permit 07020358
Permit Number 07020358
Review Stop B
Sequence Number 1
Notes
Date Text
2007-03-29 09:30:00DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO LEGIBLE COPIES OF THE PRODUCT APPROVALS.
  
 4)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 5)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 6) SUBMIT PRODUCT APPROVALS FOR THE GLASS BLOCK AND
 SINGLE HUNG WINDOW.
  
 7) THE PRODUCT APPROVAL NOA SUBMITTED FOR THE PGT
 SGD-70, SLIDING GLASS DOOR, HAS BEEN REVISED BY NOA #
 06-0523.03. SUBMIT CURRENT NOA.
  
 8)SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES LISTED
 IN THE NOA FOR THE FIRESTONE MODIFIED ROOF SYSTEM WILL
 BE INSTALLED. INDICATE THE FASTENING OPTION THAT WILL
 BE USED AND DESIGN PRESSURE FOR THE SELECTED ASSEMBLY
 BY CIRCLING THE APPROPRIATE ITEMS ON THE NOA. THE
 REQUIRED UPLIFT PRESSURES ARE -59.2 FOR ROOF ZONE 2 NAD
 -89.0 FOR ROOF ZONE 3. IF THE DESIGN PRESSURES ARE TOO
 LOW FOR THESE AREAS, SUBMIT RAS 117 CALCULATIONS IF
 ALLOWED BY GENERAL LIMITATION #7 ON PAGE 34 OF THE
 NOA.
  
  
 9) SHOW COMPLIANCE WITH R404.1.6 HEIGHT ABOVE FINISHED
 GRADE.
 CONCRETE AND MASONRY FOUNDATION WALLS SHALL EXTEND
 ABOVE THE FINISHED GRADE ADJACENT TO THE FOUNDATION AT
 ALL POINTS A MINIMUM OF 4 INCHES (102 MM) WHERE MASONRY
 VENEER IS USED AND A MINIMUM OF 6 INCHES (152 MM)
 ELSEWHERE.
  
 10) SHOW COMPLIANCE WITH SECTION 704 INSPECTION FOR
 TERMITES.
 IN ORDER TO PROVIDE FOR INSPECTION FOR TERMITE
 INFESTATION, CLEARANCE BETWEEN EXTERIOR WALL COVERINGS
 AND FINAL EARTH GRADE ON THE EXTERIOR OF A BUILDING
 SHALL NOT BE LESS THAN 6 INCHES (152 MM). EXCEPTIONS:
 1.PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS
 THAN 5 / 8 INCH (17.1 MM) THICK ADHERED DIRECTLY TO THE
 MASONRY FOUNDATION SIDEWALL.
 2.ACCESS OR VEHICLE RAMPS WHICH RISE TO THE
 INTERIOR FINISH FLOOR ELEVATION FOR THE WIDTH OF SUCH
 RAMPS ONLY.
 3.A 4-INCH (102 MM) INSPECTION SPACE ABOVE PATIO
 AND GARAGE SLABS AND ENTRY AREAS.
 4.IF THE PATIO HAS BEEN SOIL TREATED FOR TERMITES,
 THE FINISH ELEVATION MAY MATCH THE BUILDING INTERIOR
 FINISH FLOOR ELEVATIONS ON MASONRY CONSTRUCTION ONLY.
 5.MASONRY VENEERS.
  
 11) DETAIL F1 ON S1 SHOWS A 1-1/2" X 8" RECESS AT THE
 EXTERIOR OF THE MONOLITHIC FOUNDATION AND THE WALL
 SECTION ON D1 DOES NOT. PLEASE CLARIFY.
  
 12) SHOW COMPLIANCE WITH R301.2.1.2 INTERNAL PRESSURE.
  
 WINDOWS IN BUILDINGS LOCATED IN WIND-BORNE DEBRIS
 REGIONS SHALL HAVE GLAZED OPENINGS PROTECTED FROM
 WIND-BORNE DEBRIS OR THE BUILDING SHALL BE DESIGNED AS
 A PARTIALLY ENCLOSED BUILDING IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, BUILDING . GLAZED OPENING
 PROTECTION FOR WIND-BORNE DEBRIS SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST OF ASTM E 1996
 AND OF ASTM E 1886, SSTD 12, ,OR TAS 201, 202 AND 203
 REFERENCED THEREIN.
  
 13) SHOW COMPLIANCE WITH R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN. VENTILATING OPENINGS SHALL BE
 PROVIDED WITH CORROSION-RESISTANT WIRE MESH, WITH 1 / 8
 INCH (3.2 MM) MINIMUM TO ? INCH (6.4 MM) MAXIMUM
 OPENINGS.
  
 14) SPECIFY THE LENGTH OF THE ROOF OVERHANG. SEE R320.7
 PROTECTION AGAINST TERMITES AND DECAY. CONDENSATE LINES
 AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT
 AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY
 UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS.
 GUTTERS WITH DOWN SPOUTS ARE REQUIRED ON ALL BUILDINGS
 WITH EAVES OF LESS THAN 6 INCHES HORIZONTAL PROJECTION
 EXCEPT FOR GABLE END RAKES OR ON A ROOF ABOVE ANOTHER
 ROOF.
  
 15) PROVIDE STRUCTURAL DETAILS OF THE EXISTING PORCH,
 PART OF WHICH IS BEING ENCLOSED.
  
 16) THE WRONG ENERGY CALC. FORMS WERE SUBMITTED. PLEASE
 SUBMIT THE 2004 FORMS # 600C-04 . THE OWNER/AGENT IS
 REQUIRED TO SIGN THE ENERGY CALC. FORM. SEE FBC CHAPTER
 13.
  
 17) SPECIFY THE ROOF SHEATHING FASTENER SPACING.ROOF
 SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH SECTION
 R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC RESIDENTIAL
 CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL BE FASTENED
 TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT 6 INCHES ON
 CENTER AT EDGES AND 6 INCHES ON CENTER AT INTERMEDIATE
 FRAMING. SPACING OF RING-SHANK FASTENERS SHALL BE 4
 INCHES ON CENTER IN NAILING ZONE 3 FOR 130 MPH OR
 GREATER DESIGNWIND SPEEDS IN ACCORDANCE WITH FIGURE
 R803.2.3.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  