Plan Review Notes
Plan Review Notes For Permit 07020355
Permit Number 07020355
Review Stop E
Sequence Number 2
Notes
Date Text
2007-04-25 14:28:32 
  
 ** UNSAT2ND REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THAT PLANS ARE STILL ONLY BEING
 SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN
 IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A
 *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION,
 CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH
 FINAL DOCUMENTS.
  
 2) NOTE: PLEASE SEEINFORMATION ON TITLE BLOCKS FOR
 BOTH OF THE ENGINEER AND ARCHITECT AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004.
 PLEASE ALSO SEE FLORIDA STATUTES 471.023 AND 481.219
 WHERE APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S).
 PLEASE SEE MISSING THE REQUIRED PRINTED NAME AND
 PRINTED LICENSE NUMBER OF DESIGNERS.
 PRINTED NAMES ARE REUIRED FOR ALL TITLE BLOCKS FOR
 ARCHITECT AND ENGINEER.
 ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON
 TITLE BLOCKS CAN NOT BE DONE AT THIS TIME.
 PLANS NOW CONTAIN TITLE BLOCKS, HOWEVER NOT COMPLETE
 WITH ALL INFORMATION AS REQUIRED.
  
 3) NOTE: PLEASE SEE MOST OF THE SEALS ON THE SHEETS FOR
 THE MEP ARE NOT CLEAR AND VISIBLE WITH ALL INFORMATION
 ON RAISED SEAL ESAILY READ.
 FAC 61G15-23.001.
  
 4) NOTE:THE VALUE IN RESPONSE LETTER MENTIONS WHEN
 APPLIED FOR PERMIT THE VALUE WILL BE 180K, HOWEVER
 PLEASE KNOW THAT THE VALUE SHALL INCLUDE ALL LABOR TO
 INSTALL AND VALUE FOR EQUIPMENT EVEN IF EQUIPMENT IS
 OWNER SUPPLIED. THIS VALUE SHOWN IS LOW FOR THIS
 SYSTEM.
 PLEASE KNOW THAT THE VALUE FOR THE COMPLETE SCOPE OF
 WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC SHALL
 INCLUDE ALL LABOR AND MATERIALS EVEN IF EQUIPMENT,
 ELECTRICAL PANELS ETC ARE OWNER SUPPLIED. PLEASE ADJUST
 THE APPLIED VALUE FOR ALL WORK AS SHOWN. FBC 108.3
 ADMIN SECTION.
  
 5) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL
 SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF
 CONTROL BOARDS/PANELS FROM A NRTL.
 PLEASE KNOW THAT THE INFORMATION AS SHOWN ON BASE
 BUILDING FOR SUPPLY DOES NOT PROVIDE ENOUGH INFORMATION
 FOR THIS SYSTEM.
 110.3, 90.7.
 PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS
 COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN
 BUILDING PLANS SHOWING CIRCUITING ETC.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]