Plan Review Notes
Plan Review Notes For Permit 07020355
Permit Number 07020355
Review Stop B
Sequence Number 2
Notes
Date Text
2007-05-07 11:23:26****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 ***PLAN CHECK ONLY***
  
 1-5.)ADDRESSED.
  
 6.)PLATFORM DETAIL EL X-1,2, V13, NO GUARDS SHOWN
 FBC1012.THIS COMMENT APPLIES TO OTHER SHEETS SUCH AS
 EL X-3,4.NOTE THAT THE "HANDRAIL" PLAN DOES NOT HAVE
 CROSS SECTIONS REFERRING TO THESE ELEVATIONS SO I
 CANNOT DETERMINE IF THE HANDRAIL (WHICH MAY ALSO SERVE
 AS GUARDRAILS?) IS TO BE INSTALLED IN THIS LOCATION AND
 WAS OMITTED FOR CLARITY, OR IF THE DESIGN INTENT IS FOR
 THE PLATFORM OPEN SIDES.SEE FBC1012.1, FBC1028.
  
 2ND REVIEW - A NOTE WAS ADDED STATING THAT PLATFORMS
 OVER 48" IN HEIGHT WILL HAVE HANDDRAILS.SEE
 FBC1012.1, GUARDS REQUIRED (IN ADDITION TO OTHER
 LOCATIONS WHICH MAY BE APPLICABLE) ON INDUSTRIAL
 EQUIPMENT PLATFORMS OVER 30 INCHES ABOVE THE FLOOR.
 PLEASE NOTE THAT THERE IS A DIFFERENCE BETWEEN A
 HANDRAIL AND A GUARDRAIL FBC1002. FBC1015.2
 ADDRESSES MECHANICAL EQUIPMENT PLATFORMS SPECIFICALLY.
  
 7.)SHOW ALL REQUIRED GUARDS ON THE PLAN.FOR
 INSTANCE, SEE ELEVATIONS X-3,4.SEE FBC1012, 1028.
  
 2ND REVIEW - A PLAN WAS PROVIDED BUT THE NOTE (48" HIGH
 PLATFORMS) CONFLICTS WITH CODE REQUIREMENTS OF 30".
 PLEASE REVISE THE NOTE AND REVISE HANDRAIL/GUARDRAIL
 PLAN AS REQUIRED.
  
 8.)1ST REVIEW - ARE ALL HANDRAILS SHOWN ON L1 TO ALSO
 SERVE AS GUARDRAILS?THEY APPEAR TO BE AT PLATFORM
 AREAS; HANDRAILS ARE NOT REQUIRED FOR PLATFORMS BUT
 GUARDS (GUARDRAILS) ARE.SEE OTHER COMMENTS.
  
 2ND REVIEW - THE RESPONSE, "THIS SAFETY RAIL IS FOR
 MAINTENANCE PURPOSES OF THE CONVEYOR ONLY" DOES NOT
 ADDRESS THE COMMENT.THE GUARDRAILS ARE REQUIRED,
 HANDRAIL REQUIREMENTS ARE NOT CLEAR.SEE OTHER
 COMMENTS.
  
 9.)1ST REVIEW - SEE ELEVATIONS X-1,2, SECTION DETAIL
 V7, 3.1. THIS DETAIL IS TOO SMALL TO READ.THE SHEETS
 ARE LABELED BUT NOT NUMBERED.DOES THIS REFER TO SHEET
 3.1 (NO 3.1 IN THE SET)?ARCHITECTURAL STANDARDS ARE
 FOR DETAIL AND SECTION INDICATORS TO REFER TO DETAIL
 AND PAGE, BUT THE DETAILS PROVIDED REFER TO SHEETS
 WHICH ARE NOT IN THE PACKAGE.PLEASE EITHER PROVIDE
 STANDARD DETAIL AND SECTION INDICATORS OR ADVISE AS TO
 HOW I COULD BEST UNDERSTAND THE PLAN.
  
 2ND REVIEW - THE SHEET PROVIDED DOES NOT HAVE A TITLE
 BLOCK AND IS NOT SEALED.PLEASE INCORPORATE ALL
 NECESSARY DETAILS INTO THE PLAN AND REMOVE UNNECESSARY
 DETAILS.OTHER SHEETS HAVE SMALL ILLEGIBLE DETAILS.
 EITHER REMOVE FROM THE PLAN OR ENLARGE SO THAT THEY ARE
 LEGIBLE.
  
 10.) ADDRESSED, BUT PLEASE SEE ELECTRIC COMMENTS.
  
 11.) THE PREVIOUS COMMENT REQUESTED CLARIFICATION FOR
 THE PURPOSE OF THE WALKS AND LANDINGS.THE PLAN NOW
 STATES IN GENERAL NOTES THAT "ALL PLATFORMS ARE FOR
 MAINTENANCE PURPOSES ONLY."PLEASE FURTHER DESCRIBE
 THE USE OF THE LANDINGS AND WALKS."MAINTENANCE ONLY";
 IS THIS TO OCCUR ON OCCASION SUCH AS ONCE A MONTH, OR
 SEVERAL TIMES IN THE DAY?COMPLIANCE WITH VERTICAL
 ACCESSIBILITY (EXCEPTION) APPEARS TO BE CLEAR, BUT
 EGRESS REQUIREMENTS ARE NOT CLEAR.
  
 PLEASE INCORPORATE THIS INFORMATION ON THE ISO SHEET
 WHICH MAKES IT APPEAR THAT THE LANDINGS ARE WORK
 AREAS.
  
  
 NEW COMMENTS;
  
 12.)CLEARLY INDICATE ALL CHANGES TO THE PLAN WITH
 CLOUDS AND REVISION NUMBERS. SEVERAL SHEETS CHANGED
 WITH NO REVISIONS SHOWN.
  
 13.)SHEET A, ELEVATIONS X-1, 2 HAS A DETAIL V7 3.1
 WHICH IS TOO SMALL TO BE LEGIBLE.ALL INFORMATION ON
 THE PLAN IS TO BE LEGIBLE.CHECK ALL SHEETS, ALL
 DETAILS.
  
 14.)THE GENERAL NOTES REFER TO THE CONVEYOR SAFETY
 CABLE RAIL LOCATIONS.REQUIRED GUARDS ARE TO COMPLY
 WITH FBC1012, FBC1607.7.PLEASE STATE STRUCTURAL
 DESIGN CRITERIA ON THE PLAN AND PROVIDE A DETAIL
 SHOWING COMPLIANCE WITH FBC1012.THE DETAIL AS DRAWN
 IS NOT TALL ENOUGH AND THE OPENINGS ARE TOO LARGE TO
 REJECT A 21" OBJECT.CODE COMPLIANCE IS NOT CLEAR.