2007-03-04 15:40:41 | ** UNSAT ** |
| |
| 1) NOTE: PLEASE KNOW THAT PLANS HAVE ONLY BEEN |
| SUBMITTED FOR *PLAN REVIEW* ONLY AND HAVE NOT BEEN |
| SUBMITTED FOR PERMIT APPLICATION. PLEASE KNOW THAT EVEN |
| IF ELECTRICAL WAS OK, THE PLANS WOULD STILL REMAIN IN A |
| *F* STATUS UNTIL THE TIME THAT THE PERMIT APPLICATION, |
| CONTRACTOR, VALUATION ETC CAN BE REVIEWED ALONG WITH |
| FINAL DOCUMENTS. |
| |
| 2) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN |
| SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH WILL |
| AFFECT DESIGNS FOR ALL TRADES |
| |
| 3) NOTE: PLEASE SEE MISSING TITLE BLOCKS FOR BOTH OF |
| THE ENGINEER AND ARCHITECT AS REQUIRED UNDER FLORIDA |
| ADMINISTRATIVE CODES 61G15-23.002, 61G1-16.004. PLEASE |
| ALSO SEE FLORIDA STATUTES 471.023 AND 481.219 WHERE |
| APPLICABLE FOR REQUIRED FIRM LICENSE NUMBER(S). PLEASE |
| SEE MISSING THE REQUIRED PRINTED NAME AND PRINTED |
| LICENSE NUMBER OF DESIGNERS. |
| ** REVIEW OF TITLE BLOCKS AND INFORMATION REQUIRED ON |
| TITLE BLOCKS CAN NOT BE DONE AT THIS TIME. |
| |
| 4) NOTE: PLEASE BE SURE ALL SEALS ARE CLEAR AND VISIBLE |
| WITH ALL INFORMATION ON SAID SEAL. THE PE SEAL IS VERY |
| FAINT AND INFORMATION IS NOT EASILY READ. 61G15-23.001 |
| |
| 5) NOTE: ***IMPORTANT*** |
| PLEASE SEE ATTACHED DOCUMENTATION FROM THE DEPARTMENT |
| OF BUSINESS AND PROFESSIONAL REGULATION / STATE'S |
| WEBSITE WHICH SHOWS THE LICENSE FOR JAMES PURDY, PE # |
| 14240 AS *DELINQUENT*/ EXPIRED. |
| ONE SET OF PLANS TO BE RETAINED. |
| |
| 6) NOTE: PLEASE KNOW THAT THE VALUE FOR THE COMPLETE |
| SCOPE OF WORK FOR THE CONVEYOR SYSTEM, ELECTRICAL, ETC |
| SHALL INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| EQUIPMENT, ELECTRICAL PANELS ETC ARE OWNER SUPPLIED. |
| PLEASE ADJUST THE APPLIED VALUE FOR ALL WORK AS SHOWN. |
| FBC 108.3 ADMIN SECTION. |
| |
| 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON ELECTRICAL |
| SYSTEM(S). PLEASE PROVIDE INFORMATION ON LISTINGS OF |
| CONTROL BOARDS/PANELS FROM A NRTL. |
| 110.3, 90.7. |
| PLEASE LIST ON RECORD SET OF PLANS WHERE POWER ETC IS |
| COMING FROM. THIS SHOULD CORRELATE WITH THE MAIN |
| BUILDING PLANS SHOWING CIRCUITING ETC. |
| |
| 8) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS. |
| |
| 9) NOTE: PLEASE SEE SEVERAL SHEETS FROM THE ARCHITECT |
| IN EACH SET ARE NOT SIGNED, DATED AND SEALED AS |
| REQUIRED. PLEASE SEE SOME SHEETS WHERE IT APPEARS THE |
| DESIGNER STARTED TO SIGN PLANS AND STOPPED MID-POINT? |
| 481.221. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |