Plan Review Notes For Permit 07020339 |
Permit Number |
07020339 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-11-11 11:02:55 | **PROVISO** REVISED AC-1 THRU AC-4 DELTA 4 | | | | PG AC-1: REVISE PLAN TO COORDINATE SIZE OF FLEX DUCT | | FEEDING THE FIRST FLOOR. THE SECOND FLOOR PLAN SHOWS | | THIS AS 12 INCH ROUND WHILE THE FIRST FLOOR PLAN SHOWS | | THIS SAME DUCT AS 8 INCH ROUND. WHICH IS CORRECT? | | | | PG AC-2: BEDROOM 2 BATHROOM EXHAUST DUCT IS MSSING | | SIZE. DRYER EXHAUST DUCT IS MISSING SIZE. REVISE PLAN | | TO SHOW MISSING DUCT SIZES. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|