Notes
Date Text
2007-03-12 12:41:29DENIED
 REFERENCE: FBC-2004 W/2006 AMENDMENTS
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PLEASE INDICATE CODE REFERENCES ON PLANS. SECTIONS
 106.1.1 & 106.1.2.
  
 2. SHT 2 OF 6A INDICATES 3" DUAL RPZV BACKFLOW
 PREVENTERS ON 4" DIP WATER LINE. PER TABLE 603.1(D),
 ALL BACKFLOW ASSEMBLIES SHALL BE AT LEAST THE SAME SIZE
 AS THE LINE IN WHICH THEY ARE INSTALLED.4" DUAL RPZV
 BACKFLOWS ARE REQUIRED.
  
 3. SHT A103 ROOF PLAN NOTE POINTS TO A 4"X8" "TRANSFER
 SCUPPER" AND INDICATES (TYP OF 2), BUT ONLY ONE SHOWN.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 4. SHT A103 ROOF PLAN NOTED "TRANSFER SCUPPER" IS SHOWN
 AS 4"X8", WHEREAS SHT P-3 INDICATES THE "TRANSFER
 SCUPPER" AS 4"X6". PLEASE CORRELATE THE INFORMATION
 BETWEEN THE TWO SHEETS. SECTION 106.1.1.
  
 5. SHT P-5 WATER RISER DIAGRAMS DO NOT REFLECT THE
 FLOOR PLAN FOR THE REF. & THE WATER SERVICE ROUTING FOR
 BOTH UNITS. PLEASE CORRELATE. SECTION 106.1.1.
  
 6. SUBMIT A HORIZONTAL STORM RISER ISOMETRIC RISER, AND
 VERTICAL STORM RISER DIAGRAMS. SHOW ALL PIPE SIZES, AND
 INDICATE SQUARE FOOTAGE AS IT ACCUMULATES IN THE
 SYSTEM. SECTION 106.3.5.1.3(7)(13) & TABLE 1106.3.
  
 7. SHT IR-1 IRRIGATION PLANS ARE INCOMPLETE. SHOW ALL
 PIPING AND INDICATE PIPE SIZE. SHOW THE LOCATION OF THE
 METER, BACKFLOW PREVENTER, & RAIN SENSOR. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]