Date |
Text |
2007-03-15 10:20:48 | --------------DENIED---------------- |
| |
| FBC 2004 W/ 2006 REVISIONS |
| FRC 2004 |
| FBC,M 2004 |
| |
| 1. BUILDING PLAN SHOWS A UNIT A AND A UNIT B, AC PLAN |
| SHOWS BOTH TO BE UNIT A. FOR PURPOSE OF CLARITY, PLEASE |
| CORRELATE DRAWINGS. FBC 106.1.1 |
| |
| 2. PG AC-2 1ST FLOOR: PLEASE INDICATE THE SIZE OF THE |
| DUCT BETWEEN THE 16X6 TRANSFER GRILLS. FBC 106.1.1 |
| |
| 3. PG AC-2 1ST FLOOR: LEFT UNIT SHOWS 10X6 DUCT DOWN TO |
| 1ST FLOOR. THIS DUCT IS ALREADY ON THE FIRST FLOOR. |
| SHOULD IT SAY ?UP TO 2ND FLOOR?? FBC 106.1.1 |
| |
| 4. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL |
| BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M |
| 1107.2.1. |
| |
| 5. PG AC-2 1ST FLOOR: RIGHT UNIT SHOWS A 10X6 DUCT UP |
| TO 1ST FLOOR. SHOULD THIS SAY ?UP TO 2ND FLOOR?? ALSO, |
| PLEASE SHOW SIZE OF DIFFUSER AND CFM AT 4? ROUND FLEX |
| DUCT TERMINATIONS. PLEASE CLARIFY. FBC 106.1.1 |
| |
| 6. PG AC-2 2ND FLOOR: LEFT UNIT SHOWS 22X8 DUCT UP TO |
| 2ND FLOOR. DUCT IS ALREADY ON 2ND FLOOR. SHOULD IT SAY |
| ?UP TO 3RD FLOOR?? ALSO, REFRIGERANT LINES ARE SHOWN |
| GOING UP WHERE THEY SHOULD BE GOING DOWN AS WELL AS |
| GOING DOWN WHERE THEY SHOULD BE GOING UP. PLEASE |
| CLARIFY. FBC 106.1.1 |
| |
| 7. PG AC-2 2ND FLOOR: RIGHT UNIT FE-1 EXHAUST DUCT IS |
| SHOWN GOING OUT SOUTH EXTERIOR WALL WITH NO WALL CAP. |
| THERE IS ALSO A 4? ROUND DUCT GOING UP TO THE 3RD FLOOR |
| FROM NOWHERE. PLEASE CLARIFY. FBC 106.1.1 |
| |
| 8. PGS AC-2 AND AC-3: PLEASE REMOVE CLOUDS FROM DRAWING |
| FOR THE PURPOSE OF CLARITY AS THERE ARE YET TO BE ANY |
| REVISIONS. |
| |
| 9. PG AC-3: DOOR SCHEDULE INDICATES LOUVERED DOORS ON |
| A/C CLOSET. A SOLID DOOR W/ GASKET SHOULD BE USED AS |
| THIS CLOSET IS BEING USED AS A PLENUM AND THE DRAWING |
| OF RETURN AIR FROM A CLOSET IS PROHIBITED UNDER FRC |
| M1602.2(5) |
| |
| 10. PG AC-3 EF-1 IN BOTH ROOMS LABELED ?BATH 2? THERE |
| IS A 4? ROUND DUCT GOING TO A 5? ROUND ROOF CAP. IS |
| THIS INTENTIONAL OR A MISTAKE? ALL OTHER ROOF CAPS |
| MATCH THE CORRESPONDING DUCT SIZE. |
| |
| 11. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM |
| THAT IS IN COMPLIANCE WITH FRC 1411.3.1 |
| |
| 12. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS |
| ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1 |
| |
| 13. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES |
| OF ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT |
| REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M |
| TABLE 401.6 AND FRC M1501.1 |
| |
| 14. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC |
| 2004 W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT |
| AND RESUBMIT. |
| |
| IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE |
| FEEL FREE TO CONTACT ME AT ANY TIME. |
| |