2007-03-15 10:20:48--------------DENIED----------------
  
 FBC 2004 W/ 2006 REVISIONS
 FRC 2004
 FBC,M 2004
  
 1. BUILDING PLAN SHOWS A UNIT A AND A UNIT B, AC PLAN
 SHOWS BOTH TO BE UNIT A. FOR PURPOSE OF CLARITY, PLEASE
 CORRELATE DRAWINGS. FBC 106.1.1
  
 2. PG AC-2 1ST FLOOR: PLEASE INDICATE THE SIZE OF THE
 DUCT BETWEEN THE 16X6 TRANSFER GRILLS. FBC 106.1.1
  
 3. PG AC-2 1ST FLOOR: LEFT UNIT SHOWS 10X6 DUCT DOWN TO
 1ST FLOOR. THIS DUCT IS ALREADY ON THE FIRST FLOOR.
 SHOULD IT SAY ?UP TO 2ND FLOOR?? FBC 106.1.1
  
 4. PG AC-2 PIPING IN OR BENEATH CONCRETE FLOORS SHALL
 BE ENCASED IN A PIPE DUCT PER FRC R101.2, FBC,M
 1107.2.1.
  
 5. PG AC-2 1ST FLOOR: RIGHT UNIT SHOWS A 10X6 DUCT UP
 TO 1ST FLOOR. SHOULD THIS SAY ?UP TO 2ND FLOOR?? ALSO,
 PLEASE SHOW SIZE OF DIFFUSER AND CFM AT 4? ROUND FLEX
 DUCT TERMINATIONS. PLEASE CLARIFY. FBC 106.1.1
  
 6. PG AC-2 2ND FLOOR: LEFT UNIT SHOWS 22X8 DUCT UP TO
 2ND FLOOR. DUCT IS ALREADY ON 2ND FLOOR. SHOULD IT SAY
 ?UP TO 3RD FLOOR?? ALSO, REFRIGERANT LINES ARE SHOWN
 GOING UP WHERE THEY SHOULD BE GOING DOWN AS WELL AS
 GOING DOWN WHERE THEY SHOULD BE GOING UP. PLEASE
 CLARIFY. FBC 106.1.1
  
 7. PG AC-2 2ND FLOOR: RIGHT UNIT FE-1 EXHAUST DUCT IS
 SHOWN GOING OUT SOUTH EXTERIOR WALL WITH NO WALL CAP.
 THERE IS ALSO A 4? ROUND DUCT GOING UP TO THE 3RD FLOOR
 FROM NOWHERE. PLEASE CLARIFY. FBC 106.1.1
  
 8. PGS AC-2 AND AC-3: PLEASE REMOVE CLOUDS FROM DRAWING
 FOR THE PURPOSE OF CLARITY AS THERE ARE YET TO BE ANY
 REVISIONS.
  
 9. PG AC-3: DOOR SCHEDULE INDICATES LOUVERED DOORS ON
 A/C CLOSET. A SOLID DOOR W/ GASKET SHOULD BE USED AS
 THIS CLOSET IS BEING USED AS A PLENUM AND THE DRAWING
 OF RETURN AIR FROM A CLOSET IS PROHIBITED UNDER FRC
 M1602.2(5)
  
 10. PG AC-3 EF-1 IN BOTH ROOMS LABELED ?BATH 2? THERE
 IS A 4? ROUND DUCT GOING TO A 5? ROUND ROOF CAP. IS
 THIS INTENTIONAL OR A MISTAKE? ALL OTHER ROOF CAPS
 MATCH THE CORRESPONDING DUCT SIZE.
  
 11. PLEASE SHOW AN AUXILIARY OR SECONDARY DRAIN SYSTEM
 THAT IS IN COMPLIANCE WITH FRC 1411.3.1
  
 12. PLEASE INDICATE ON PLAN WHERE R-4.2 DUCT IS
 ACCEPTABLE AND WHERE R-6 DUCT IS REQUIRED. FBC 106.1.1
  
 13. PLEASE PROVIDE DETAIL ON PLAN SHOWING WHICH TYPES
 OF ROOF/WALL CAPS ARE TO BE USED AS THERE ARE DIFFERENT
 REQUIREMENTS FOR BATHROOM AND DRYER EXHAUST. SEE: FBC,M
 TABLE 401.6 AND FRC M1501.1
  
 14. GENERAL NOTE #15: THIS PROJECT IS UNDER FBC/FRC
 2004 W/ 2006 REVISIONS, NOT FBC 2001. PLEASE CORRECT
 AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS REGARDING THIS REVIEW, PLEASE
 FEEL FREE TO CONTACT ME AT ANY TIME.
  