Plan Review Notes
Plan Review Notes For Permit 07020336
Permit Number 07020336
Review Stop P
Sequence Number 6
Notes
Date Text
2009-11-16 18:39:47DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-4 UNIT B SANITARY ISOMETRIC RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN. THE TUB IN THE MASTER BATH
 IS NOT INDICATED ON THE RISER DIAGRAM. SECTION 106.1.1
 & SECTION 701.1.
  
 2. SHT P-6 DOES NOT SHOW ANY REVISION. PLEASE INDICATE
 THE LOCATION OF THE REVISION WITH A REVISION NUMBER AND
 CLOUD EACH REVISION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  