Plan Review Notes For Permit 07020336 |
Permit Number |
07020336 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2009-11-11 12:52:23 | **PROVISO** REVISED AC-1 THRU AC-4 DELTA 4 | | | | 1. PG AC-1: REVISE PLAN TO SHOW MISSING EXHAUST FANS, | | EXHAUST DUCTS AND TERMINATION LOCATIONS. | | | | 2. PG AC-2: REVISE PLAN TO SHOW MISSING EXHAUST DUCTS, | | SIZES AND TERMINATION LOCATIONS. | | | | 3. PG AC-2: RETURN AIR TRANSFER DUCTS ARE NOT SIZED TO | | MEET THE EXCEPTIONS UNDER FBC-R M1602.4. A FIELD TEST | | WILL BE REQUIRED AT TIME OF FINAL INSPECTION TO VERIFY | | PRESSURE DIFFERENTIAL UNLESS DUCTS ARE SIZED TO MEET | | THE EXCEPTIONS UNDER THIS SECTION. IF DUCT SIZES ARE | | CHANGED, REVISE PAN ACCORDINGLY. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|