2009-11-11 12:52:23**PROVISO** REVISED AC-1 THRU AC-4 DELTA 4
  
 1. PG AC-1: REVISE PLAN TO SHOW MISSING EXHAUST FANS,
 EXHAUST DUCTS AND TERMINATION LOCATIONS.
  
 2. PG AC-2: REVISE PLAN TO SHOW MISSING EXHAUST DUCTS,
 SIZES AND TERMINATION LOCATIONS.
  
 3. PG AC-2: RETURN AIR TRANSFER DUCTS ARE NOT SIZED TO
 MEET THE EXCEPTIONS UNDER FBC-R M1602.4. A FIELD TEST
 WILL BE REQUIRED AT TIME OF FINAL INSPECTION TO VERIFY
 PRESSURE DIFFERENTIAL UNLESS DUCTS ARE SIZED TO MEET
 THE EXCEPTIONS UNDER THIS SECTION. IF DUCT SIZES ARE
 CHANGED, REVISE PAN ACCORDINGLY.
  