Plan Review Notes For Permit 07020336 |
Permit Number |
07020336 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-04-30 19:26:57 | -------------DENIED--------------- | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | PREVIOUS COMMENTS FOR CONTINUITY. | | | | 1. OK | | | | 2. OK | | | | 3.DRYER EXHAUST TERMINATION AT ROOF REQUIRED | | BACKDRAFT DAMPER PER FRC M1501.1. | | | | 4. OK | | | | 5. REFRIGERANT PIPE DETAIL SHOWS CONDENSATE FROM | | AUXILIARY DRAIN PAN BEING DISCHARGED THRU AUXILIARY | | WATER HEATER LINE. WATER HEATER IS NOT SHOWN IN A/C | | CLOSET ON PLUMBING PLANS. AUXILIARY DRAIN PAN FOR A/C | | CONDENSATE SHOULD HAVE EITHER A FLOAT SWITCH OR A | | SECONDARY DRAIN LINE PIPED TO A CONSPICUOUS LOCATION | | PER FRC M1411.3.1. CONDENSATE OVERFLOW CAN NOT BE | | DISCHARGED INTO AN AUXILIARY WATER HEATER LINE AS IT | | WILL NOT PROVIDE WARNING OF A PROBLEM WITH THE PRIMARY | | CONDENSATE DRAIN. | | | | 6. OK | | | | 7. OK | | | | REVIEWED BY: | | RONALD J REGUEIRO | | 561.805.6719 | | [email protected] |
|