2007-04-30 19:26:57-------------DENIED---------------
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS COMMENTS FOR CONTINUITY.
  
 1. OK
  
 2. OK
  
 3.DRYER EXHAUST TERMINATION AT ROOF REQUIRED
 BACKDRAFT DAMPER PER FRC M1501.1.
  
 4. OK
  
 5. REFRIGERANT PIPE DETAIL SHOWS CONDENSATE FROM
 AUXILIARY DRAIN PAN BEING DISCHARGED THRU AUXILIARY
 WATER HEATER LINE. WATER HEATER IS NOT SHOWN IN A/C
 CLOSET ON PLUMBING PLANS. AUXILIARY DRAIN PAN FOR A/C
 CONDENSATE SHOULD HAVE EITHER A FLOAT SWITCH OR A
 SECONDARY DRAIN LINE PIPED TO A CONSPICUOUS LOCATION
 PER FRC M1411.3.1. CONDENSATE OVERFLOW CAN NOT BE
 DISCHARGED INTO AN AUXILIARY WATER HEATER LINE AS IT
 WILL NOT PROVIDE WARNING OF A PROBLEM WITH THE PRIMARY
 CONDENSATE DRAIN.
  
 6. OK
  
 7. OK
  